D9412GV2/D7412GV2 | Program Entry Guide | 6.0  GV2AUX 
EN | 128 
 
 
Bosch Security Systems, Inc. | 10/08 | F01U003636-04 
6.4 SDI 
RPS 
Parameters 
6.4.1  User Interface Modifications for 
COMMAND 43 
Configure remote programming software (RPS) 
parameters when communicating over a private local-
area network (LAN) or wide-area network (WAN). To 
allow RPS to communicate with a control panel over 
a LAN or WAN, an SDI-Ethernet two-way network 
interface module (NIM) and an RPS (version 3.8 or 
higher) are required. The computer on which RPS is 
installed needs a network card. See your information 
systems administrator for network requirements. 
COMMAND 43 can communicate with RPS by a 
network path. Figure 6 on page 26 shows the 
structure of COMMAND 43. 
Pressing the [ESC] key during the display of 
CONTACT RPS?, ANSWER NOW?, RPS VIA 
PHONE?, or RPS VIA NETWORK? exits the user to 
Idle Text. 
Enable SDI RPS 
This section allows you to:  
 
• 
• 
• 
• 
Define the RPS parameters necessary to 
communicate by an external modem that can be 
connected to a D9133DC Direct Connect 
Programming Module. 
Default: 
Yes 
Selection: 
Yes or No 
Enable RPS sessions over the SDI 
bus. 
Yes 
Provide for local programming by a DX4010i or 
D9133DC Serial Interface Module. 
Do not enable RPS sessions over 
the SDI bus. 
No 
Provide remote programming by a Conettix 
DX4020 or D9133TTL-E Ethernet Network 
Interface Module. 
Enable SDI RPS determines if the control panel 
allows RPS communications over the SDI bus. This 
item must be set to Yes if you plan to use the 
external modem configuration, a private LAN or 
WAN, or local RPS programming. 
Provide enhanced route paths for event reporting 
through a network using a DX4020 Network 
Interface Module. 
Although not listed in this section, RPS checks for the 
RPS pass code (refer to Section 2.7 RPS Parameters 
on page 32), Datalock Code, and control panel type 
to determine if this RPS session should continue.  
 
 
 
The RPS via Phone? prompt (Figure 6 
on page 129), if selected, contacts RPS 
by the control panel phone line and not 
the external modem. Users cannot start 
an RPS session by the external modem. 
If you are using an external modem, RPS 
sessions can be started only by 
programming Answer Armed and Answer 
Disarmed (to a value greater than 0) or 
by setting RPS Line Monitor to Yes 
(refer to Section 6.4.2 Using an External 
Modem
 on page 130). 
 
If the reset pin is in the locked position, 
local RPS programming is allowed even 
if this prompt is set to No
 
 
When Enable SDI RPS is configured to 
allow for local programming, Jumper 8 in 
the SIM must be shorted or closed, 
 
power must be removed and reapplied 
after changing the address, and a 
standard serial null-modem cable is 
required.