Bosch Appliances Video Game Controller D9412GV2 User Manual

Page of 158
D9412GV2/D7412GV2 | Program Entry Guide | 6.0  GV2AUX 
EN | 139 
 
 
Bosch Security Systems, Inc. | 10/08 | F01U003636-04 
 
 
RTS Control 
Default: 
On 
Selection: 
On, AutoX, Off, AutoR 
On 
Sets RTS to on (hardware control). 
Auto X 
Automatically enables Xon/Xoff 
(software control). 
Off 
Sets RTS off (hardware control). 
Auto R 
Sets this to Auto RTS. 
Determines how the Request To Send (RTS) control 
parameters are defined for the network interface 
module (NIM). Pressing the [SPACE] bar on the 
D5200 toggles through the available options. 
 
 
Set this item to On when using the 
External Modem feature. 
 
DTR Control 
Default: 
On 
Selection: 
On, AutoD, Off 
On 
Sets DTR to on (hardware control). 
AutoD 
Sets this to Auto DTR. 
Off 
Sets DTR off (hardware control). 
Determines how the Data Terminal Ready (DTR) 
control parameters are defined for the network 
interface module (NIM). Pressing the [SPACE] bar on 
the D5200 toggles through the available options. 
 
 
 
Set this item to On when using the 
External Modem feature. 
 
9133 Supervision 
Default: 
No 
Selection: 
Yes or No 
Yes 
Supervise the network interface 
module (NIM). 
No 
Do not supervise the network 
interface module (NIM). 
This item determines whether the NIM is supervised. 
If the NIM is supervised, disconnecting it from the 
control panel creates a Trouble SDI 88 Event and the 
keypad annunciates a trouble tone and displays  
SERVC SDI 88. 
Trouble SDI 88 Reports are always 
reported using the account number for 
Area 1. 
 
 
6.7 
Route Group Attempts 
This section determines how many times a route 
group tries the primary destination before trying the 
backup destination if the primary destination fails. 
This entry applies to both Phone numbers and IP 
addresses. 
RG# 1 Attempt 
Default: 
No 
Selection: 
Yes or No 
This route group tries the primary 
destination once and, if 
unsuccessful, tries the backup 
destination. The control panel still 
makes a total of ten attempts (five to 
the primary, five to the backup) 
before generating a route group 
Comm Fail Event. 
Yes 
This route group tries the primary 
destination twice and, if 
unsuccessful, tries the backup 
destination. The control panel makes 
a total of ten attempts (six to the 
primary, four to the backup) before 
generating a route group Comm Fail 
Event. 
No 
6.8 Miscellaneous 
Fire Summary Sustain 
Default: 
No 
Selection: 
Yes or No 
Forces the Summary Fire relay 
output to remain on after the Alarm 
Silence command. 
Yes 
Allows Summary Fire relay output 
to be silent when the Fire Alarm Bell 
output is silenced and all Fire Points 
return to normal. 
No 
Use this parameter to set the Summary Fire relay 
output to continue or to stop after the Fire Alarm Bell 
is silenced or times out. Refer to the Summary Fire 
prompt in Section 2.13.2 Panel-Wide Relays on 
page 82.