D9412GV2/D7412GV2 | Program Entry Guide | 6.0  GV2AUX 
EN | 141 
 
 
Bosch Security Systems, Inc. | 10/08 | F01U003636-04 
 
 
 
 
Swinger Count 
To meet UL requirements, the combined 
Entry Delay time and Abort Window time 
Default: 
must not exceed 60 sec. For Entry Delay 
time programming information, refer to  
P## Entry Delay in the Point Responses 
section of your control panel’s program 
entry guide. 
UL note: Maximum settings for 
residential use:  
Exit Delay – 120 sec 
Entry Delay = 45 sec bell 
Off-Premise Transmission = 60 sec 
Maximum settings for commercial use: 
Exit Delay – 120 sec no line security 
Entry Delay = 60 sec bell 
Off-Premise Transmission = 60 sec 
The system must use both the bell and  
off-premise transmission. 
Selection:  1, 2, 3, or 4 
1, 2 
Number of fault or trouble bypasses 
allowed per hour for SIA CP-01 
compliance. 
Optional fault count 
Value used for backward 
compatibility with previous control 
panel operation. 
When a point has P# Swinger Byps set to Yes, the 
value set in Swinger Count determines the number 
of times the point is faulted erroneously within an hour 
before it is automatically bypassed.  
For SIA CP-01 Compliance: 
P## Swinger Byps
 can be Yes or No. 
If P## Swinger Byps is YesSwinger Count must 
be 1 or 2. 
Passcode Length 
Remote Warning 
Default: 
Selection:  0, 3, 4, 5, or 6 
Default: 
Yes 
Selection: 
Sets a variable length for user 
passcodes, allowing for backward 
compatibility 
Yes or No 
Yes 
The system uses the Alarm Bell 
output to annunciate the arming and 
disarming of an area through remote 
software, or a remote arming device 
such as a key switch or key fob. 
3, 4, 5, 
or 6 
Sets a fixed length to all user 
passcodes. 
During entry delay, the code is accepted when the 
last digit is pressed to disarm the area.  
No 
No remote warning occurs to 
annunciate the arming and disarming 
of an area through remote software, 
or a remote arming device such as a 
key switch or key fob. 
For SIA CP-01 Compliance: 
Passcode Length
 must be set to 3, 4, 5, or 6. 
Upon remote arming, the output pulses on for 2 sec. 
Upon remote disarming, the output pulses on, off, on, 
off for 2 sec each. 
For SIA CP-01 Compliance 
Remote Warning
 must be set to Yes