Bosch Appliances Video Game Controller D9412GV2 User Manual

Page of 158
D9412GV2/D7412GV2 | Program Entry Guide | 7.0  RADXAXS 
EN | 148 
 
 
Bosch Security Systems, Inc. | 10/08 | F01U003636-04 
 
D# Deact On Open? 
D# REXShunt Only? 
Default: 
Yes 
Default: 
No 
Selection: 
Yes or No 
Selection: 
Yes or No 
Yes 
Strike deactivates when the door is 
opened after a valid Access Granted 
request. 
Programmed shunt time activates 
so the door can be manually 
opened. 
Yes 
No 
Strike remains activated for the 
amount of the programmed strike 
time whether door is opened or 
closed. 
REX automatically activates the 
programmed strike and shunt time. 
No 
Use this program item to disable the door strike, but 
activate the programmed D# Shunt Time upon a 
request to exit (REX) from an area. 
Determines if the strike deactivates immediately upon 
physically opening the door. 
 
 
In order for this function to work, a point 
needs to be assigned to the door. 
 
 
 
To Reduce False Alarms, maintain D# 
Deact on Open?
 as the default (Yes). 
This helps prevent the door from 
bouncing open and causing a false 
alarm. 
 
D# RTE Shunt Only? 
Default: 
No 
Selection: 
Yes or No 
Yes 
Programmed shunt time activates 
so door can be manually opened. 
No 
RTE automatically activates the 
programmed strike and shunt time. 
Use this program item to disable the strike, but still 
activate the programmed shunt time at a Request to 
Enter (RTE) area. 
 
 
Use this parameter when a user can 
open a door manually without relying on 
a token or card to activate the strike 
(such as with a push bar). 
 
 
 
When RTE Shunt Only is Yes, RTE 
Events are not logged, reported, or 
printed. 
 
Use this parameter when a user can 
open a door manually without relying on 
a token or card to activate the strike 
 
(such as with a push bar). 
 
When REXShunt Only is Yes, REX 
Events are not logged, reported, or 
printed. 
 
 
7.3 Event 
Profile 
This programming category is used to determine if 
events are created for: 
• 
• 
• 
Access Granted and Access Denied 
Door Requests 
Door state changes due to manual (keypad) or 
automatic scheduled or armed state changes 
(skeds/hold open on disarm, normal on armed) 
operation. 
Door # 
Default: 
Selection: 
1 to 8 
Enter the door you plan to program. 
RTE Events require Access Granted to 
be programmed as Yes