D9412GV2/D7412GV2 | Program Entry Guide | 2.0  GV2MAIN 
EN | 19 
 
 
Bosch Security Systems, Inc. | 10/08 | F01U003636-04 
 
 
 
Test Reports 
 
Restoral Reports are not sent if the 
control panel resets after a point is 
bypassed and then unbypassed. This is 
true for both Fire and Non-fire points. 
To meet UL 864 requirements for 
Central Station and Remote Station 
applications, enable Test Reports
 
User Reports 
Sending Test Reports 
Automatic:
 To send a single Test Report (R# Test 
Report
) automatically, enable Sked Function Code 
#9 (Test Report) in the Skeds section of the program. 
Refer to 
Selecting Yes enables a report to be sent when the 
event occurs. 
Table 12: User Reports 
Manual: To send a single Test Report manually, 
enter [COMMAND][4][3] at the keypad. Refer to the 
 
Report 
Report Description 
Selection
 prompt on page 63
Send Report
To expand this Test Report to include any off-normal 
point condition or other off-normal system conditions, 
Expand Test Rpt (refer to page 
Yes, No 
Point Bypass Event 
R# Point 
Bypass 
12) must be 
programmed Yes. Refer to the footnotes with 
Yes, No 
Forced Point Event 
R# Forced 
Point 
14 on page 20 for a list of event types that are 
included in an expanded test report. Additionally, the 
expanded test report includes Summary Fire 
Supervisory, Summary Fire Fault, Summary 
Controlled Point Fault, and Summary Point Device 
Fault conditions. 
Yes, No 
Point Opening Event 
R# Point 
Open 
Yes, No 
Point Closing Event 
R# Point 
Close 
Yes, No 
Point Force Armed 
R# Forced 
Arm 
The control panel can generate an Expanded Off- 
Normal Test Report by using Sked Function Code 28 
or a Non-Expanded Off-Normal Test Report using 
Sked Function Code 29. To generate this event, one 
or more points must be in an off-normal state at the 
time the Sked executes. Expanded Off-Normal Test 
Reports include the Off Normal Test Report Event as 
well as a panel-wide summary of off-normal point and 
system conditions. Non-Expanded Off-Normal Test 
Report Events are sent only when a point is in the off-
normal state but sends only the Off-Normal Test 
Report Event. 
Yes, No 
Fail to Open Event 
R# Fail To 
Open 
Yes, No 
Fail to Close Event 
R# Fail To 
Close 
Yes, No 
R# Ext Clos 
Tm 
Extend Close Time 
Event 
Yes, No 
Opening Events 
R# Opening 
Rpt 
Yes, No 
R# Forced 
Close 
Point Forced Close 
Event 
Yes, No 
Closing Events 
R# Closing 
Rpt 
Sending Status Reports 
Automatic:
 To send a Status Report automatically 
that includes the events shown in the footnotes in 
Yes, No 
R# FC Perim 
Inst 
Forced Close 
Perimeter Instant 
Armed Event 
Table 13, enable Sked Function Code #10 in the 
Skeds section of the program. 
Yes, No 
R# FC Perim 
Forced Close 
Delay 
Perimeter Delay 
Armed Event 
Manual: To send a Status Report manually that 
includes the events shown in the footnotes in Table 
13
, en
ter [COMMAND][4][2] at the keypad. Refer to 
the 
Yes, No 
R# Perim Inst 
Arm 
Perimeter Instant 
Armed Event 
 prompt on page 63. 
Sending off-normal conditions as a Status Report 
following a Test Report is required by some 
automation systems. Sending off-normal conditions 
as a Non-status Report that follows a Test Report is 
required for other automation systems. 
Yes, No 
R# Perim 
Perimeter Delay 
Delay Arm 
Armed Event 
Yes, No 
User text 
R# Send User 
Text 
 
An off-normal condition is any point that is missing, 
trouble, supervisory, or in alarm. Also, points not 
cleared at the keypad report as off-normal.