D9412GV2/D7412GV2 | Program Entry Guide | 2.0  GV2MAIN 
EN | 28 
 
 
Bosch Security Systems, Inc. | 10/08 | F01U003636-04 
 
2.5 Power 
Supervision 
Table 21: Event Descriptions, Priorities, and 
Numbers, continued 
AC Fail Time 
 
Default: 
Event 
Priorit
 
 
Event Description 
Event 
Number 
Selection:  1 to 90 (Blank and 0 are invalid) 
Program the amount of time that AC power must be 
off before the control panel responds to the AC 
failure. The response to restoral of AC power is 
delayed for the same amount of time. The control 
panel always monitors AC. The response to this 
prompt is the actuation of the relay programmed in 
the Panel-Wide Relays prompt AC Failure (refer to 
Section 
Parameters Changed 
008 
054 
RPS Access OK 
008 
064 
RPS Access Fail 
008 
065 
Remote Reset 
008 
079 
Program Access OK 
n/a 
n/a 
Program Access Fail 
n/a 
n/a 
Service Start 
008 
029 
the AC Fail report enabled by the AC Fail/Res Rpt 
prompt. Local annunciation of an AC failuter is 
controlled by the AC Fail Display prompt. 
Service End 
008 
030 
Fire Walk Start 
008 
036 
Fire Walk End 
008 
037 
Walk Test Start 
008 
038 
 
Walk Test End 
008 
039 
UL 864 requirements, Section 50.2.1.b 
Extra Point 
008 
023 
states: “A trouble signal shall be 
Send Point Text 
n/a 
n/a 
transmitted for remote station, central 
RF Low Battery 
006 
093 
station, and proprietary-type protected 
RF Battery Restore 
006 
094 
premises units after a delay of between 
Date Changed 
008 
059 
60 and 180 min. 
Time Changed 
008 
060 
Exception: Products are not prohibited 
Delete User 
008 
090 
from providing capability of selecting 
User Code Change 
008 
056 
that the primary power failure trouble 
Area Watch 
008 
042 
signal transmission be delayed other 
Card Assigned 
008 
110 
time periods, including no 
Change Level 
007 
061 
delay,provided the 60 – 180 min delay 
Access Granted 
008 
003 
is also included.” 
No Entry 
008 
115 
To meet UL 864 requirements, program 
Door Left Open 
008 
116 
AC Fail Time with 61, 63, 65, ... (odd 
Cycle Door 
008 
112 
numbered values), and 89. Always 
Door Unlocked 
008 
113 
check with the Authority Having 
Door Secure 
008 
114 
Jurisdiction for local requirements. 
Door Request 
008 
117 
Door Locked 
008 
145 
 
When you program AC Fail Time, if the second digit 
is: 
User Alarm COMMAND 7 
002 
005 
User Alarm COMMAND 9 
002 
006 
• 
• 
1, 3, 5, 7, or 9 (such as 3, 5, 11, 13, 15, 21, and 
so on): The AC Fail Time interval is in minutes. 
 
 
2, 4, 6, 8, or 0 (such as 2, 4, 6, 10, 12, 20, 22, 
and so on): The AC Fail Time interval is in 
seconds. 
For the following items to be true, AC 
Fail/Res Rpt
 must be programmed as 
Yes and AC Tag Along must be 
 
programmed as No