D9412GV2/D7412GV2 | Program Entry Guide | 2.0  GV2MAIN 
EN | 36 
 
 
Bosch Security Systems, Inc. | 10/08 | F01U003636-04 
A# Acct Number 
Cancel Report 
Default: 
0000 
Default: 
No 
Selection:  For BFSK: 0000 to  0999, 
 
Selection:  Yes or No 
0BBB to 0FFF 
Yes 
Send Cancel and Fire Cancel 
Reports according to routing. 
For Modem (four-digit account 
numbers): 0000 to 9999,  
No 
Do not send Cancel and Fire Cancel 
Reports. 
BBBB to FFFF 
For Modem (ten-digit account 
A Cancel and Fire Cancel Report is created when a 
passcode is entered to silence an Alarm Bell or a Fire 
Bell before the bell time expires. 
numbers): 0000000000 to 
9999999999, BBBBBBBBBB to 
FFFFFFFFFF 
For SIA CP-01 Compliance 
Determines the account number for this area. An 
account number must be assigned to each active 
area. 
This prompt must be set to Yes
2.9 Area 
Parameters 
Account numbers are used to group areas together. 
Each area can have a different account number, or 
several areas can share the same account number. 
The control panel uses the account number as a 
reference for arming and keypad text displays. 
This programming module contains three 
programming categories: Area Parameters, Bell 
Parameters, and Open/Close Options. 
2.9.1 Area 
Parameters 
BFSK: Only the last three digits are sent. Insert a 0 
as the first digit of the account number.  
Example:  0 2 3 4. 
Area 
Default: 
2
: Enter a four-digit or ten-digit number. 
Modem IIIa
Selection:  1 to 8 
Enter the area number you are programming. 
A# Area On 
Default: 
Yes (Area 1 only) 
Selection:  Yes or No 
Yes Enable 
area. 
No Disable 
area. 
Use this program item to enable or disable the area 
specified. 
 
Area 1 must be enabled:  
•  System events such as power and 
phone supervision do not send a 
 
report correctly if Area 1 is disabled. 
•  When programmed No, points 
assigned to this area do not generate 
events, show at the keypad when 
arming and disarming, or send status 
reports. All user authority in this area 
is turned off while the area is 
disabled. 
 
 
To meet UL 864 requirements, set A# 
Area On
 to Yes