D9412GV2/D7412GV2 | Program Entry Guide | 2.0  GV2MAIN 
EN | 79 
 
 
Bosch Security Systems, Inc. | 10/08 | F01U003636-04 
Relay functions that resume the proper state 
within one minute: 
A# Fire Bell 
Default: 
Alarm Bell 
Perimeter Fault 
Summary Fire 
Summary Trouble 
Area Armed 
Reset Sensors 
Fire Bell 
AC Fail 
Summary Alarm 
Phone Fail 
Silent Alarm 
Summary SupBurg 
Area Fault 
Battery Trouble 
Summary Fire Tbl 
Communications Fail 
Watch Mode 
Summary SupFire 
Blank, 1 to 128 (1 to 64 for 
Selection: 
D7412GV2), A, B, or C 
This voltage output relay activates and provides  
12 VDC output when a Fire point (P## Fire is Yes
assigned to this area activates an alarm. 
 
Relay functions that must be reset manually 
with Change Relay function (COMMAND 54): 
Fail To Close 
Force Armed 
Duress 
Log % Full 
 
2.13.1 Area Relays 
Each area can be assigned a unique relay number for 
each of the events listed in this section. 
Area 
Default: 
Selection:  1 to 8 
Enter the area number you are programming. 
A# Alarm Bell 
Default: 
Selection: 
Blank, 1 to 128 (1 to 64 for 
D7412GV2), A, B, or C 
This voltage output relay activates and provides  
12 VDC output when a Non-fire point (P## Fire is No
assigned to this area activates an alarm. 
 
 
A# Burg Time and A# Burg Pat must be 
programmed in Area or Bell Parameters. 
This relay activates according to the bell 
pattern and remains active until the bell 
time expires or a valid passcode is 
entered. P## Silent Bell must be No for 
the bell to ring upon alarm. 
For SIA CP-01 Compliance: 
Do not set A# Alarm Bell to blank. This feature is 
required for SIA CP-01 compliance. 
Fire Time and Fire Pat must be 
programmed in Bell Parameters. This 
relay activates according to the bell 
 
pattern and remains active until the bell 
time expires. P## Silent Bell must be No 
in order for the bell to ring upon alarm. 
 
Although Relay C is a valid entry for A# 
Fire Bell
, do not program Relay C for this 
entry. Use Relay A for the A# Fire Bell
 
 
To meet UL 864 requirements, set A# 
Fire Bell
 to a value other than Blank. 
 
A# Reset Sensors 
Default: 

Blank, 1 to 128 (1 to 64 for 
Selection: 
D7412GV2), A, B, or C 
Unlike the default relay for Alarm Bell and Fire Bell, 
this voltage-output relay (Relay C) de-activates for 
5 sec when the Reset Sensors? function is activated 
from the keypad or during a Fire Walk Test. 
The Reset Sensors time converts from 
the  
5 sec default time to the time 
 
programmed in A# Verify Time (Section 
2.9
 Area Parameters on page 5) when a 
point programmed for P## Alarm Verify 
(Section 4.1 Point Index on page 88) 
enters an alarm condition.