D9412GV2/D7412GV2 | Program Entry Guide | 1.0 Introduction
EN | 8
Bosch Security Systems, Inc. | 10/08 | F01U003636-04
1.5
Guide to UL 864 Programming Requirements
This section identifies the programming requirements you must make in order to comply with UL 864
Commercial Fire applications.
Commercial Fire applications.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER
INVOLVED PARTIES
INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the
requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864,
you must limit certain programming features or options to specific values. Refer to Table 5.
requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864,
you must limit certain programming features or options to specific values. Refer to Table 5.
Table 5: UL 864 Programming Requirements
Product Feature/Option Permitted in
UL 864? (Y/N)
Possible Settings Settings Permitted in
UL 864
Refer to
Page:
Page:
If using two phone lines:
Phone 1 through 4
Phone 1 through 4
Yes
24 characters
Program a valid phone
number
number
Phone Supervision
Yes
0 to 240 sec
10 to 200 sec
Alarm On Fail
No
Yes / No
Set to No
Buzz On Fail
Yes
Yes / No
Set to Yes
Two Phone Lines
Yes
Yes / No
Set to Yes when using
PSTN communications.
PSTN communications.
Expand Test Report
Yes
Yes/No
Set to Yes
Fire Reports
Yes
Yes / No
Set to Yes
R# Fire Supervisory
Missing
Missing
Required
Yes/No
Set to Yes
Test Reports
Yes
Yes / No
Set to Yes
AC Fail Report
Yes
Yes / No
Set to Yes
AC Restoral Report
Yes
Yes / No
Set to Yes
Battery Missing Report
Yes
Yes / No
Set to Yes
Low Battery Report
Yes
Yes / No
Set to Yes
Battery Restoral Report
Yes
Yes / No
Set to Yes
RG#1 Primary SDI
Yes
Yes / No
Set to Yes
RG#1 Backup SDI
Yes
Yes / No
Set to Yes
R# Service Start Report
Required
Yes / No
Set to Yes
R# Service End Report
Required
Yes / No
Set to Yes
R# Fire Walk St Report
Required
Yes / No
Set to Yes
R# Fire Walk End Report Required
Yes / No
Set to Yes
R# Walk Test St Report
Required
Yes / No
Set to Yes
R# Walk Test End Report Required
Yes / No
Set to Yes
RG #1 Primary Device
N/A
1 to 4
Must have 1 to 4
RG #1 Backup Device
N/A
1 to 4
Must have 1 to 4
AC Fail Time
Yes
1 to 90
Enter 61
AC Fail Display
Yes
10 to 300 sec
10 to 200 sec
AC Tag Along
Yes
Yes / No
Set to Yes
AC/Battery Buzz
Yes
Yes / No
Set to Yes
Bat Fail/Res Rpt
Yes
Yes / No
Set to Yes