4.0 RADXPNTS 
4.1 Point 
Index 
Use this programming module to construct 
personality types for points used in the system. The 
Index numbers are used in Point Assignments. Each 
unique point index number determines the control 
panel’s responses to specific conditions occurring on 
the Protective points. 
The NEW RECORD program contains default entries 
and descriptions that match RPS defaults for point 
indexes. Refer to the D9412GV2/D7412GV2 
Program Record Sheet
 (P/N: F01U003635) for 
defaults. 
Point Index 
Default: 
Selection:  1 to 31 
The number of the point personality you are 
programming. You can define up to 31 individual 
personalities. 
 
 
P## Type 
Default: 
Refer to the program record sheet 
Selection: 
0 to 9, or 11 
P ## Type  
Description 
24-hour: A 24-hour point is not turned on and off from a keypad. 24-hour points are armed all 
the time, and can be used for fire protection (refer to the P ## Fire Point prompt in Section 4.2 
Point Responses
 on page 92), panic, medical, and police alerts. 
24-hour protection for fire doors, roof hatches, and so on. Instead of programming this type of 
protection as a 24-hour point, consider using a Perimeter point type with a Point Response of 
9 to E. 24-hour points do not show faults when an arming function is entered, but Perimeter 
points do. When programming this type of protection, consider also using the Buzz on Fault 
and Local While Disarmed options. 
Perimeter: Perimeter points are armed with all arming functions. Points programmed as 
perimeter can also be armed as a group (using Perimeter-Arming functions) separately from 
points programmed as interior. This lets the user partially arm the system to establish 
Perimeter protection while occupying the interior of the protected premises. 
Perimeter points can be programmed to activate entry delay time. If the point activates entry 
delay, it can also activate an entry tone. 
When a Perimeter point is programmed for entry delay, entry delay time is always provided. If 
the area is in entry delay when a second Perimeter point is faulted, the control panel 
compares the remaining entry delay time to the time programmed for the second Perimeter 
point. If the second Perimeter point’s entry delay time is less than the remaining time, it 
shortens the entry delay time. 
Perimeter points programmed for an instant point response, generate an alarm immediately 
when faulted, even during entry or exit delay.