White Rodgers 1131-102 Well Immersion Single Control Catalog

Page of 1
HYDRONIC
CONTROLS
WELL IMMERSION SINGLE CONTROL
Types for use as High Limit, Reverse Action or SPDT Switching 
Action: May Be Mounted Either Horizontal or Vertical.
FEATURES
• Extra capillary length for extended shank wells.
• Special screw terminals with “ears” securely hold solid and stranded wires.
• Screwdriver-adjustable differential with direct-read indicator.
• Knockouts on top and bottom and plenty of wiring room.
• Hydraulic action element — fast acting.
SPECIFICATIONS
Dimensions. . . . . . . . . . . . . . . . . . . . . . . .   5
3
/
8
H + 2
5
/
16
 coil x 2
9
/
16
D
Finish . . . . . . . . . . . . . . . . . . . . . . . . . . . .   Grey
Agency . . . . . . . . . . . . . . . . . . . . . . . . . . .   U.L. listed and C.S.A. approved
11D18-1
PARTS AND ACCESSORIES 
See end of this section for additional parts and accessories
• F145-0163 — Tube heat conductive compound
• Immersion wells — see page 107
 
 
 
 
 
Full 
Motor Rating 
Valves and
 
Model 
 
 
 
Switch 
Electrical 
(Full Load) 
Relays
  Number 
Range 
Differential 
Action 
Rating 
120 VAC 
240 VAC
 
24 VAC 
0.3-12v DC
 
11D18-1  ➀ 
100 to 240°F 
5 to 45°F 
Open on Rise 
HTV 
10.0A 
6.0A 
6.0A 
1.0A
 
 
(38 to 116°C) 
(3 to 25°C) 
 
See page 416
 
 
 
 
 
11D31-1
100 to 240°F
7 to 45°F
SPDT
HH
7.4A
3.7A
2.9A
 
 
(38 to 116°C) 
(4 to 25°C) 
 
See page 416
Has U.L. approved adjustable dial stop, factory set at 150°F maximum.
TYPES WITH BULBS DIRECTLY INTERCHANGEABLE WITH HONEYWELL 
(3
9
/
16
” x 
3
/
8
No wells included.
SPDT Contact Structure
HH Rated Controls
Switch Action
R-B Open on Rise
R-W Close on Rise
 
 
 
 
 
Full 
Motor Rating 
Valves and
 
Model 
 
 
 
Switch 
Electrical 
(Full Load) 
Relays
  Number 
Range 
Differential 
Action 
Rating 
120 VAC 
240 VAC
 
24 VAC 
0.3-12v DC
 
1131-102  
100 to 240°F
7 to 45°F
SPDT
HH
7.4A
3.7A
2.9A
 
 
(38 to 116°C) 
(4 to 25°C) 
 
See page 416
 
 
 
 
 
11B18-101  ➀ 
100 to 240°F 
5 to 45°F 
Open on Rise 
HTV 
10.0A 
6.0A 
6.0A 
1.0A
 
 
(38 to 116°C) 
(3 to 25°C) 
 
See page 416
 
 
 
 
 
Has U.L. approved adjustable dial stop, factory set at 150°F maximum.
TYPES WITH TAPERED BULBS 
(2
7
/
16
” x 
7
/
16
All types include 
1
/
2
” 
standard shank well, unless otherwise specified.
CONTRACTOR TIP: 
TESTING AUTOMATIC TEMPERATURE CONTROLS To verify a control is opening and closing properly, disconnect 
all power before testing. Testing must be performed with the sensing element at a temperature within the setting range of the control. For 
most hydronic controls with a range of 100 to 240°F, a pan of hot water is sufficient to reach the control range.
Attach an ohmmeter or continuity tester across the Open on Rise contacts. Lower the temperature setting dial to the lowest setting. 
If the lowest setting is below the temperature of the sensing element minus the differential of the control, the contacts should be open. 
Raise the temperature dial slowly. When the setting is raised above the temperature of the sensor, the contacts should close.
www.white-rodgers.com