White Rodgers 230-22 Temperature Control for Heating Catalog

Page of 1
WARM AIR 
CONTROLS
TEMPERATURE CONTROLS FOR HEATING
Provide Regulation of Duct Temperatures in Conjunction with Air Handling Units or
Control of Circulator for Indoor-Outdoor Regulation from a Remote Point
FEATURES
•  Hydraulic action element – Unaffected by vibration.
•  Switch case mounts in any position – No leveling required. Includes bulb mounting clip.
•  High electrical rating permits operation of most equipment without use of relays
  or motor starters.
•  Dustproof steel case – Dial visible and can be adjusted through cover. Case has
 knockouts on top and bottom.
•  Temperature dial graduated in °F and °C.
230-22
SPECIFICATIONS
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . .   5
3
/
4
H x 2
5
/
16
 W x 2
9
/
16
D
Finish . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   Grey
Agency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   U.L. listed and C.S.A. approved
 
 
 
 
 
Full 
Motor Rating 
Resistive
 
Model 
 
 
Capillary 
Bulb 
Switch 
Electrical 
(Full Load) 
(Non-inductive)
  Number 
Range 
Differential 
Length 
Size 
Action 
Rating 
120 VAC  240 VAC  120 VAC  240 VAC
 
230-22  
20 to 120°F
Adj. 4 to 30°F
8 ft.
6
1
/
4
 x 
3
/
8
 
Open on 
FG 
14.0A 
7.0A 
25.0A 
22.0A
 
 
(-6 to +49°C) 
(2.2 to 17°C) 
 
 
Rise
 
See page 416
U.L. approved adjustable dial stop, factory set at 90°F maximum.
FLUSH MOUNT FAN OR LIMIT CONTROLS / 
ATTIC FAN CONTROL
Ideal for Replacement of Similar Type Controls
FEATURES
• For use where space is limited.
• Small bimetal sensing element.
• Snap-Action switch.
• Fan control has adjustable range with direct reading temperature dial.
758 has adjustable limit setting.
SPECIFICATIONS
Dimensions for 758. . . . . . . . . . . . . . . . . .   1”H x 3”W x 1
1
/
4
D
Dimensions for 775. . . . . . . . . . . . . . . . . .   2.8”H x 3.59”W x 2.02”D
775-1
 
Model 
 
 
 
Switch 
Motor Rating – Full Load 
Pilot
  Number 
Description 
Range 
Differential 
Action 
120 VAC 
240 VAC 
Duty
 
758-1 
Limit 
110 to 200°F ➀ 
Fixed 25°F 
Open on Rise 
8.0 A 
4.0 A 
125 VA
 
 
 
(43 to 93°C) 
(14°C)
 
775-1 
Attic Fan Control 
60 to 120°F ➁
Fixed 10°F
Close on Rise
9.0 A
 
 
with Thermal Limiter 
(15 to 49°C) 
(6°C)
 Cut-out setting (cut-in is cut-out setting minus the differential)
 Thermal limiter opens at 183°F (84°C)
758-1
FAN / LIMIT
www.white-rodgers.com
64
HEA
TING