0508082120/101203/C
Page 8
Owner’s manual
Technical Repair Guide
• Press W: medium HV level (7300 V); leds • and •• are 
burning.
• Press W: low HV level (7100 V); led • is burning.
• Press V: to increase efficiency again up to maximum HV 
level (7900 V); leds •, ••, ••• and •••• are burning.
• Press 
PROGRAM
: confirm setting 5 and go to setting 6.
Program Setting 6: Maximum fan speed remote control/
panel button
In setting 6 
STANDBY
 led will flash six times every two seconds. 
Adjusting the maximum fan speed for remote control/panel 
button is very convenient for air cleaners installed in meeting 
rooms and open plan offices.
• Default: •••• (
TURBO
).
• Press W and so on to go to the desired maximum fan speed.
• Press 
PROGRAM
: confirm setting 6 and go to setting 7.
Program Setting 7: Sensitivity adjustment Air Quality 
Analyzer
In setting 7 
STANDBY
 led will flash seven times every two 
seconds. 
Setting the sensitivity of the Air Quality Analyzer. The more 
sensitive, the quicker the reaction to changes in pollution level. 
• Default: 
OFF
 (all leds are off), meaning the lowest sensitivity
• Press V: led • (
LOW
) will light up, meaning you've set the 
pollution sensitivity to low.
• press V: led •• (
MEDIUM
) will light up, meaning you have set 
the pollution sensitivity to medium.
• Press V: led ••• (
HIGH
) will light up, meaning you have set 
the pollution sensitivity to heavy.
• Press V: led •••• (
TURBO
) will light up, meaning you have set 
the pollution sensitivity to extreme.
• If you want to go back to one of the previous pollution 
sensitivity, press W.
• Press 
PROGRAM
 to confirm setting 7 and go to setting 8.
Program Setting 8: Time without high voltage after 
Service (Electronic Air Cleaners only)
In setting 8 
STANDBY
 led will flash eight times every two 
seconds. 
Setting a specific time for no high voltage after servicing is 
useful when the filter cells are damp or condensed in winter 
time. This setting will go back to default value if power is 
interrupted to the air cleaner.
• Default: 
OFF
 (all leds are off), when the air cleaner is 
switched on, there's always high voltage on the cell(s).
• Press V: led • (
LOW
) will light up, meaning you've set the 
time of no high voltage to 30 minutes.
• Press V: led •• (
MEDIUM
) will light up, meaning you've set 
the time of no high voltage to 60 minutes.
• Press V: led ••• (
HIGH
) will light up, meaning you've set the 
time of no high voltage to 120 minutes.
• Press V: led •••• (
TURBO
) will light up, meaning you've set 
the time of no high voltage to 240 minutes. 
• If you want to go back to one of the previous time setting 
levels, press W.
• Press 
PROGRAM
 to confirm setting 8. The air cleaner will 
return to the normal running mode.
Reset to factory default 
To reset the factory default settings:
Open the inlet grid, press the panel button (>> ). While pressing 
the panel button (>> ) close the inlet grid. Release the panel 
button (>> ) when you hear two beeps.
Everything is now back into the default setting, except the 
Service Indicator (hours in use).
9
FILTER REPLACEMENT/CLEANING
See fig. 8 on page 25
In order to open the inlet grid (i.e. access the filter components), 
a narrow round screwdriver type tool will be needed (such as a 
torx type). The inlet grid is secured by two mechanical clips. To 
release these clips there are two access holes parallel to the 
control board faceplate on the inlet grid (approx. 3½" from the 
sides). 
Insert the tool into the access holes and gently push further 
through some light resistance. This will allow the clips to be 
"unlocked" and thus the inlet grid will open easily.  
DO NOT PULL THE DOOR OPEN WITHOUT RELEASING THE 
CLIPS.
9.1
Prefilter replacement
The disposable prefilter can only be used once and cannot be 
cleaned. Do not turn the prefilter around since it can only be 
used in one flow direction.
9.2
Electronic filter cleaning
A crackling or snapping sound will be heard occasionally during 
use of the air cleaner. This is normal and is caused by high 
voltage arcing in the filter. Cleaning the electronic filter is 
necessary when the crackling is heard frequently.
 
For maximum efficiency your air cleaner cell(s) should be 
cleaned regularly. When cleaning is required the following 
procedure should be used:
Cleaning the cell(s)
A Turn the air moving system 
OFF
 and disconnect the air 
cleaner from power. Wait 15 seconds for the collecting 
cell(s) to discharge.
B Remove the cell(s) and prefilter(s) from cabinet. Using a 
solution of warm water and low sudsing detergent, soak 
cell(s) for 20 to 30 minutes. Discard prefilter(s) and carbon 
filter(s).
NOTE: Ionizing wires may become coated causing loss of 
cleaning ability by the collecting cell. Using a damp cloth, 
wipe each ionizing wire, exercising care not to damage 
them.
CAUTION
CELLS MAY CONTAIN SHARP EDGES.
Use care when servicing unit or handling cells. Failure 
to do so could result in minor personal injury.
!