Residual Current Calculation (I4)
Chapter 5 - Features and Applications 
Page 131
Changing the Meter Password
1.
Select S
ECURITY
 from the Setup menu.
2.
You will see that the screen displays 00000. Enter the current password. If you 
have not previously changed your password, the default is 00000.
3.
Choose M
ODIFY
 P
ASSWORD
 to alter your password (the F
ACTORY
 U
SE
 O
NLY
 
option is for factory purposes and is not accessible).
4.
Enter your new numeric password.
To change the value of the highlighted digit use the Up and Down arrow 
buttons. 
To change the position of the cursor one space to the left, hold the Up arrow 
button for about one second. 
To change the position of the cursor one space to the right, hold the Down 
arrow button for about one second.
5.
Select Y
ES
 to accept your new password. You will be returned to the Setup 
menu.
Residual Current Calculation (I4) 
The Power Meter module provides an output register labeled “I4” which holds the 
residual current value, derived from the three phase current measurements. As 
such, I4 represents the ground fault current, or the current flow in the neutral or 
ground conductor.
This quantity is only available when the meter's Volts Mode is set to 4-W
IRE
 W
YE
. If 
the Power Meter module is set to any other Volts Mode, the I4 output will read N
OT
 
A
VAILABLE