Siemens 9330 User Manual

Page of 176
9300 Series User’s Guide
Meter Clock Configuration
Chapter 3 - Default Meter Functionality 
Page 49
Fine Tuning Over Condition Monitoring
If you want to fine-tune over condition monitoring, the only setup registers you 
should change are SusUntlON and SusUntlOFF
SusUntlON determines how long the modules wait after an over condition is 
detected before reporting it. This gives the monitored value a short period to 
correct itself before the event is registered with the module, so that very brief over 
conditions are ignored. Similarly, SusUntlOFF is the amount of time a normal 
value must be present before the module considers normal operation to be 
restored. Both SusUntlON and SusUntlOFF values are entered in seconds (the 
default value for both is 30 seconds).
Refer to the online ION Programmer’s Reference for more information about the 
Relative Setpoint module.
Meter Clock Configuration
The Clock module controls the meter’s internal clock which provides timestamps 
for data logged by the device. The clock needs to be configured properly to ensure 
that logged data has accurate timestamp information. The Clock module also 
receives the time synchronization signals sent to it by the workstation running 
ION software, updating the device’s clock when required.
The setup registers in the Clock module specify timezone and Daylight Savings 
Time (DST) parameters and time synchronization functions. 
N
OTE
When modifying setup registers of the Clock module, use the Format option to convert between UNIX and
conventional time. Refer to the description of the Clock module in the online 
ION Programmer’s
Reference
 for more details.
Refer to the technical note Time Synchronization and Timekeeping for further details 
on using the meter’s time synchronization functions.
Setup Register
Function
Default
TZ Offset
The timezone the device is in, relative to Greenwich Mean Time
0
DST Start
Date and time when DST begins
0
DST End
Date and time when DST ends
86,400
DST Offset
The amount of time the clock is changed when DST begins or ends
0
Time Sync Source
The communications port that receives time sync signals
COM1
Time Sync Type
The type of time sync signal (Local or Universal time)
UTC
Clock Source
Specifies the clock’s time synchronization signal source (line frequency, communications signals, or 
internal crystal)
Internal