CONFIGURE THE COMMUNICATIONS TAB
1. Connection Type:  Specify the type of connection between the device driver and the alarm unit. 
DIRECT SERIAL: The alarm unit is connected using an RS-232 to RS-422 converter or using an RS-422 PC serial port. 
INTERNET PROTOCOL: The alarm unit is connected to the serial port on a networked device. 
MODEM: This feature is reserved for future development. 
2. Settings:  Complete the instructions provided below for the appropriate connection type specified in Step 1. The settings must match the 
settings specified within the alarm unit. Refer to the CM9760-ALM installation/operation manual for information on unit settings.
Direct Serial Settings
Figure 110.  Communications Tab for CM9760-ALM Serial Settings
a.
Select the COM port the alarm unit is connected to from the drop-down box. 
b.
Set the baud rate to match the Port 0 DIP switch settings on the alarm unit. 19200 is recommended. If the alarm unit is daisy-chained 
from another alarm unit, use the same baud rate for all the units in the chain.
c.
The remaining settings should specify no parity, 8 data bits, 1 stop bit, and no flow control.
d.
Refer to Step 3 for instructions on completing the fields in the Miscellaneous section.
Internet Protocol Settings
Figure 111.  Communications Tab for CM9760-ALM IP Settings