PART 1  AD268
3.  Input Type Setting
3.2  Parameter setting by software
The input range of the AD268 is specified by writing the following parameter data into the
AD268's buffer memory. To access the buffer memory, T2 user program (READ and WRITE
instructions) is required.
When the parameter is set to the AD268, it is saved in the AD268's built-in EEPROM.
Therefore, once the input type parameter is set, there is no need to execute the input type
setting operation.
T2 CPU
AD268
Input type parameter data:
Input type
Parameter
data
Voltage input
Current input
0
0 to 5V
0 to 20mA
1
0 to 10V
2
1 to 5V
4 to 20mA
4
±
5V
5
±
10V
AD268 buffer memory address:
H8018
Input type for channel 1
H8019
Input type for channel 2
H801A
Input type for channel 3
H801B
Input type for channel 4
H801C
Input type for channel 5
H801D
Input type for channel 6
H801E
Input type for channel 7
H801F
Input type for channel 8
The factory setting is 
±
10V range.
For details of the procedure to set the input type parameter, refer to section 6.
Buffer memory
User program
WRITE
READ
EEPROM