Fujitronic Programmable Operation Display UG520H-x User Manual

Page of 275
2 - 32
MITSUBISHI PLC • 5
(FX series link [A prt] )
11
19200bps
Even
7
Normally RS-232C
MODE 1
Baud Rate
Parity
Transmission
Code
Data Length
Stop Bit
1
Function
H/W Type
Sumcheck
Transmission Control Mode
Item
Setting of PLC
19200bps
Even
7
1
*
1
Comm. Parameter of POD
Exclusive Protocol Communication (fixed)
Provided (fixed)
RS-232C
Trans. Mode 1
FX2N
FX2N-232-BD
FX2N-485-BD
FX2N-422-BD
FX1N-232-BD
FX1N-485-BD
FX1N-422-BD
FX0N-232ADP
FX0N-485ADP
FX0N-232ADP
FX0N-485ADP
Select PLC Type
PLC
Link Unit
Wiring Diagram
RS-232C [Wiring Diagram 1]
RS-485 [Wiring Diagram 3]
RS-422 [ UG00C-E ] made by Fuji Electric 
RS-232C [Wiring Diagram 1]
RS-485 [Wiring Diagram 3]
RS-422 [ UG00C-E ] made by Fuji Electric 
RS-232C [Wiring Diagram 2]
RS-485 [Wiring Diagram 3]
RS-232C [Wiring Diagram 2]
RS-485 [Wiring Diagram 3]
FX series
(A protocol)
FX1N
FX1S
FX0N
FX2NC
Available PLC
Communication Setting
The recommended communication parameter setting of both PLC and POD is as follows:
*
1
When the link unit, FX2N-485-BD, FX2N-422-BD, FX1N-485-BD,FX1N-422-BD or
FX0N-485-ADP is used, select [RS-485] in [Signal Level].
At the [Detail Setting] menu of the [Comm. Parameter] dialog of UG00S-CW,
setting the value more than [2] in [Send Delay Time] is recommended.
11 MITSUBISHI PLC 
 5