Fujitronic Programmable Operation Display UG520H-x User Manual

Page of 275
2 - 133
Telemecanique PLC
Available PLC
52
52 Telemecanique PLC
Communication Setting
The recommended communication parameter setting of both PLC and POD is as follows:
TSX Micro
PLC
Wiring Diagram
RS-485
[Wiring Diagram 1]
Select PLC Type
TSX Micro 
Connection
9600bps
Odd
8 (fixed)
Baud Rate
Parity
Transmission
Code
Data Length
Stop Bit
1
Item
Setting of PLC
Multi-Link (fixed)
9600bps
 Odd
1
Comm. Parameter of POD
Available Memory
Set the memory to the extent of the memory range of each PLC model.
Use TYPE number to assign indirect memory for macro programs.
Memory
TYPE
Remarks
MW (memory Word)
0
KW (constant word)
1
M
(bit memory)
2
Wiring
The following is a diagram to show the wiring of the cable which connects POD to PLC.
RS-485
Wiring Diagram 1
POD  (CN1)
D-sub  25pin(Male:     )
FG
+SD
-SD
+RD
-RD
1
SG
7
12
13
24
25
D+
D-
PLC
MiniDIN 9pin(Male:    )
1
2
0V
7
* Use twist shielded cables.