PntCheckSum Parameter
The PntCheckSum is a CRC-16 checksum of the Configuration Parameters of a point. 
Most points have the PntCheckSum parameter; a few like the CLK (Clock) Point, DIAG 
(Diagnostics) Point, and the register points (BREG, IREG, and DREG) do not. Any time a 
Configuration Parameter is changed, the TankGate re-calculates the checksum. The 
PntCheckSum is used at initialization to validate each point in the database. 
PntStatus Parameter
The PntStatus parameter gives information about point execution. Refer to the 
information provided for each Software Block about the particular use of the PntStatus 
parameter.
Elapse Parameter 
The Elapse parameter usually indicates the time of the last point execution. It is used as 
the basis for automatic Change of State notifications.
Value Parameter
The Value parameter indicates the real-time value of the point. In the case of DI points, 
the Value represents a Coded value (i.e., On, Off, Opened, Closed, etc.) AI points 
represent the Value in an IEEE floating point format. In most cases, the Value parameter 
is one of the most important parameters for a point.
Level & Temp Parameters
The Level & Temp parameters indicate the real-time tank level and temperature of the 
tank gauge point. There are many Software Blocks available in the TankGate associated 
with tank gauge communications, including Software Blocks for every major tank gauge 
manufacturer.