Introduction 
Siemens Building Technologies, Inc. 
 3 
Hardware Outputs  
Analog (0 to 10V)  
Application 
•  Cooling valve actuator 
2281, 2283, 2287 
•  Face-bypass damper actuator 
2281, 2283, 2284, 2286 
•  Heating valve actuator 
2281, 2283, 2284, 2286, 2287 
•  Outdoor air damper actuator 
2281, 2283, 2284, 2286 
 
Digital 
Application 
•  Auxiliary radiation electric coil contact; or, 
auxiliary radiation two-position valve actuator 
2281, 2283, 2284, 2286 
• Unit 
fan 
2281, 2283, 2284, 2286, 2287 
•  First stage electric heat 
2281, 2283, 2284, 2286 
•  Second stage electric heat 
2281, 2283, 2284, 2286 
•  Third stage electric heat 
2281, 2283, 2284, 2286 
•  Two-position cooling valve actuator 
2281, 2283, 2284, 2286 
•  Two-position heating valve actuator 
2281, 2283, 2284, 2286 
• DX 
coil 
2284, 2286, 2287 
Power Wiring 
The controller is powered by 24 Vac and connects to the two screw terminals on the 
controller. Labeled “C” (Common) and “H” (Hot) on the terminal block labeled “24 VAC”. No 
earth-ground connection is required (Figure 2). 
Communication Wiring 
The controller connects to the field panel by means of a Floor Level Network (FLN) trunk. 
Communication wiring connects to the three screw terminals on the controller labeled “+” 
(positive), “-“ (negative), and “S” (Shield) (Figure 3).