Applications 
Basic Operation 
The Unit Vent Controller
⎯0 to 10V Output provides Direct Digital Control (DDC) technology 
for unit ventilator applications. The applications available in this controller are as follows: 
• 
Heating and/or Chilled Water Cooling,  
ASHRAE Cycles l and II  
 
Application 2281
 
• 
Heating and/or Chilled Water Cooling,  
ASHRAE Cycle III 
 
Application 2283
 
• 
Heating and DX Cooling,  
ASHRAE Cycles I and II  
 
Application 2284
 
• 
Heating and DX Cooling,  
ASHRAE Cycle III 
 
Application 2286
 
• 
Nesbitt Cycle W  
Application 2287
 
• 
Slave Mode (no control; available for set up,  
and point extension device) 
 
Application 2299
 
Control Temperature Setpoints 
The controller maintains a specified temperature setpoint based on Day/Night mode, the 
heating/cooling mode, or the setpoint dial (if used). 
Day/Night Mode 
The controller maintains the specified day setpoint temperature during daytime hours and the 
specified night setpoint at night. 
Day Heating Operation 
The controller maintains the room temperature by resetting the unit ventilator's discharge 
temperature setpoint (2281/2284), modulating the available coil control device, controlling 
auxiliary radiation (if provided), positioning the outdoor air or face-bypass damper.