Siemens 125-1957 User Manual

Page of 48
 
Siemens Building Technologies, Inc. 
 
23 
Point Database 
This chapter presents a description of the Unit Vent Controller database including point 
descriptors, point addresses, and a listing of applications in which each point is found. 
Table 3.  Point Database. 
Descriptor Address 
Application 
Description 
CTLR ADDRESS 
01 
2281, 2283, 
2284, 2286, 
2287, 2299 
Identifies the controller on the FLN trunk. 
APPLICATION 02 
2281, 
2283, 
2284, 2286, 
2287, 2299 
The identification number of the program running in the 
controller. 
Valid entries: 2281, 2283, 2284, 2286, 2287, 2299 
ROOM TEMP 
04 
2281, 2283, 
2284, 2286, 
2287, 2299 
Actual reading from the room temperature sensor. 
HEAT.COOL 05  2281, 
2283, 
2284, 2286, 
2287 
Current mode of operation for applications that can be either a 
heating mode or a cooling mode. 
DAY CLG STPT 
06 
2281, 2283, 
2284, 2286, 
2287 
The temperature setpoint in degrees that the controller 
maintains, during day periods in cooling mode, if a room 
temperature sensor setpoint dial is not present or is not used. 
Refer to STPT DIAL (Point 14). 
Valid entry range: 48° to 95°F (9°- 35°C) 
DAY HTG STPT 
07 
2281, 2283, 
2284, 2286, 
2287 
The temperature setpoint in degrees that the controller 
maintains during day periods in heating mode if a room 
temperature sensor setpoint dial is not present or is not used. 
Refer to STPT DIAL (Point 14). 
Valid entry range: 48° to 95°F (9° to 35° C) 
NGT CLG STPT 
08 
2281, 2283, 
2284, 2286, 
2287 
The temperature setpoint in degrees that the controller 
maintains during night periods in cooling mode.  
Valid entry range: 48° to 95°F (9° to 35°C) 
NGT HTG STPT 
09 
2281, 2283, 
2284, 2286, 
2287 
The temperature setpoint in degrees that the controller 
maintains during night periods in heating mode. 
Valid entry range: 48° to 95°F (9°to 35°C) 
OADPR MINPOS 
10 
2281, 2283, 
2284, 2286, 
2287 
The minimum position the damper will be commanded to during 
day mode.