Siemens TV Converter Box 611 User Manual

Page of 324
System integration 
 
7.1 System requirements 
Permissible voltages 
The SIMODRIVE 611 drive system is dimensioned for direct operation on TN line supply 
systems. The following table shows the permissible rated voltages of TN line supply systems 
that apply to the motors. 
Table 7- 1 
Permissible rated voltages of TN line supply systems, resulting DC link voltages and 
converter output voltages 
Permissible line 
supply voltage 
Resulting DC link voltage U
ZK
 
Drive output voltage (rms value) 
U
amax
 
400 V  
600 V (controlled) 
540 V (uncontrolled) 
425 V (controlled) 
380 V (uncontrolled) 
480 V  
648 V (uncontrolled) 
460 V (uncontrolled) 
In combination with the drive system SIMODRIVE 611, the motors are generally approved 
for operation on TN and TT networks with grounded neutral and for IT networks. A protective 
device should be provided for operation on IT networks, which switches off the drive system 
in the case of a ground fault. In operation with a grounded external conductor, an isolating 
transformer with grounded neutral (secondary side) must be connected between the supply 
and the drive system to protect the motor insulation from excessive stress. 
Adaptation transformers that have been tailored to the system are available for operation on 
IT or TT line supply systems. 
Requirements 
●  The power unit is selected depending on the motor current at torque M
0
 and a speed 1 
[rev/min] or according to the maximum motor current. 
●  The motors should be set up as synchronous rotation motors (SRM). 
●  The encoder system used must be harmonized with the particular application. 
 
Drive systems 
The following SINUMERIK/SIMODRIVE systems are suitable:  
●  SIMODRIVE 611 digital with High-Performance or High-Standard control modules in 
conjunction with SINUMERIK 840 D or SINUMERIK 810D 
●  SIMODRIVE 611 universal HRS 
●  SINUMERIK 810D CCU-3 
 
 
1FW6 Built-in torque motors 
106
 
Configuration Manual, 05/2009, 6SN1197-0AD00-0BP7