8.3 Cooler connection 
NOTICE 
 
With 1FW6 built-in torque motors featuring single-core power cables without a PE cable, a 
connection point is provided for the PE. A separate PE cable must be connected to this to 
ensure a direct connection to the power unit. 
 
8.2.4 
Requirements for the motor supply cables 
Motor supply cables 
The length of the power and signal cables from the motor to the converter must not exceed 
50 m. 
 
NOTICE 
 
The permissible acceleration rates of the cables must be carefully taken into consideration. 
In particular, this applies when the cables are routed via a tow chain. 
To prevent wear and tear, the cables fixed permanently to the motor should not be routed 
via a tow chain because they cannot be replaced if they are damaged. 
 
Also refer to integrating into the system. Data for the motor supply cables: see "Overview" 
and catalog NC 60. 
Specification of the motor supply cables 
The built-in torque motors are supplied with MOTION-CONNECT cables according to 
Catalog NC 60 from which you can take the technical data: 
Power cable: MOTION-CONNECT 800, type 6FX8 
Signal cable: MOTION-CONNECT 700, type 6FX7 
8.3 
Cooler connection 
Cooler connection for motors with a cooling jacket 
The cooler for motors with a cooling jacket is connected via the built-in construction. The 
cooling water cable cross-sections depend on the cross-sections of the cooling slots in the 
jacket. These slots are sealed by means of the housing provided by the customer and the O-
rings. 
In the case a built-in torque motor with a cooling jacket, the coolant must be 
supplied/discharged via two holes (cut by the user) in the axes construction (see following 
diagrams). For information on the installation hole fit, refer to the section titled "Installation 
drawings/Dimension drawings". 
 
1FW6 Built-in torque motors 