this displays the output voltage and current of the 
battery you are charging. ( a less current but higher voltage ) 
( this is the setup information screen )  This screen gives different 
information depending on the system cycle, it is informing you., WET  OPEN= wet open lead acid cell batteries, 
this  shows that the  system battery type dip switches are set for wet cell batteries,( 14.8 v max setting ) Bulk 
charge refers to the initial charge rate, this could change to a timer, then adventually change to float ( float 
charger 14 volts )
                
  This screen shows the time left to the next pause cycle  
( for 2.5 min. ) and that it is on auto. The auto can be removed by pushing buttons 1 and 2 together. This 
removes the auto pause control, and the charger will still have all its safety and timing cycles, every 20 min. 
pause
 R:v2.0 C:v2.0, this shows the software version for 
remote ( R ) and for main PCB ( C ). the 12vIN-12vOUT, refers to the motel, a 12v-12v unit. There are 12-24 v, 
24-24 and 24-12.
:  There are 2 x screens on this button. Push once for screen a, then 
again for screen b. Screen a shows the alternator temp and the domestic battery temp, if the temperature 
sensors are not fitted it will default to 20 deg C
 Temp 4a+b:  There are 2 x screens on this button. Push once 
for screen a, then again for screen b. Screen b shows the box heat sink temperatures, LHS stands for left hand 
side, Guess what RHS stands for.
Do not expect these to be the same temperature
Pre set voltages: 
Minimum input voltage the unit will run at    13 volts
Voltage the unit switches off and drops into sleep mode 
           below 12.8 v for at lease 15 mins
Power consumption on sleep mode. 5 ma ie 0.005 amps
max input voltage trip 15.5
max output voltage trip 15.5
Alt temp disengage    100 deg C
Reset alt                        80
Battery temp trip           50 deg C
Heat sink trip                  70 deg C
Heat sink reset               60 deg C
Fans on at                     50 deg C
Fans on over                 35 amps 
Fans of at                       45 deg C
Low battery alarm          1 2.5 v
Low battery regulation    13 v 
high battery voltage trip 15.5v
Max input current  at 12 v = 45 amps
amp meter +/- about 10%
voltmeter +/- 1%
 Push button marked 2 again: screen E/b 
Screen F/a: Push button marked 3 
 Push button marked 3 again: screen F/b.
                Push button marked 3 again: screen F/c.
Screen G/a:  Push button marked 4.
                Screen G/b::  Push button marked
( x 2 for 24 v models )
All voltages refer to a default temperature of 20 deg c
if the battery temperature sensor is fitted these voltages will be less depending on 
the battery temperature