Application Considerations
Horizon OAU Operation
The Horizon™ OAU can use either DX cooling, condenser reheat, electric or gas heat to condition 
outdoor air. The unit controls modulate cooling and heating capacity, reducing the supply air 
temperature swings associated with staged heating and cooling.
OAU with Reheat
 shows the OAU system with a DX refrigerant circuit design using reheat.
Dehumidification
. If the outdoor air dew point is above the dehumidification setpoint (or in 
the case of zone control, the zone RH is above the RH setpoint), the OAU will:
cool the outdoor air to remove required moisture and 
reheat to meet the discharge temperature setpoint. 
Figure 3.
Indirect discharge to fan-coil units
Figure 4.
Refrigeration system diagram with reheat
 
 
Main Condenser 
Reheat Coil 
Main Evaporator 
Expansion Valves 
Compressors 
Indoor Fan