Power and Grounding Requirements
 
   5-9
 
DMS-MTX DualMode Metrocell Cell Site Description
 
Cable Identification
 
It is a current practice to label or color-code insulated conductors. The 
following table shows the labeling and colors of insulated wires used in North 
America.
Framework Ground or Framework Bonding conductors are also known as 
"Protective Earth" as per IEC-950. The 50/50 green yellow ratio must be no 
less than 30% and no more than 70% for either color. 
 
Note:  
 
Countries outside North America may have different labeling and 
color coding of cables. Follow the safety standards for installation and 
maintenance of electrical equipment in your country accordingly.
 
Table 5-2
Cable identification - North America
Conductor Potential
Function
Label
Color Code (if used)
 
+24 Vdc
dc power
L+
(typically black with a 
tag)
0 V (grounded side of 
the +24 Vdc power 
supply)
dc power return, 
battery return, 
BR conductor
L-
(typically black with a 
tag)
-48 Vdc /-60 Vdc
dc power
L-
(typically black with a 
tag)
0 V (grounded side of 
the -48/-60 Vdc power 
supply)
dc power return, 
battery return, BR 
conductor
L+
(typically black with a 
tag)
grounded (or bonded 
to ground)
framework ground, 
framework bonding 
conductor
FG
green (50%) yellow 
(50%)
grounded (or bonded 
to ground)
ac equipment 
grounding conductor
none
green (N. America) 
green + yellow 
(Europe)