Mitsubishi Motors Oven FR-A5AP User Manual
57
5.5. Setting Example
When the frequency is set to 0 to 60Hz at the input pulse frequency setting of 0 to 50kpps.
NFB
IM
FR-A5AP
Hz
0
60
50kpps
0 to 50kpps
0 to 60Hz
Power supply
Frequency setting potentiometer
e.g. pulse
generator
generator
Inverter
Motor
Pr
ese
t fr
eque
n
c
y
Input pulse frequency
R
(L1)
S
(L2)
T
(L3)
U
V
W
1) From the maximum number of input pulses, calculate the Pr. 384 "input pulse frequency division ratio" value.
Pr. 384 =
Maximum number of input pulses(pps)
400
=
50000
= 125
Set 125 in Pr. 384.
400
2) Set the zero-input pulse frequency and maximum-input pulse frequency.
Pr. 385 = 0Hz
Pr. 386 = 60Hz
Pr. 386 = 60Hz
<Example> The following is the calculation of the minimum frequency that may be detected using the above setting
example:
Minimum frequency
example:
Minimum frequency
=
Pr. 386
2
16.6ms
Pr. 384
400
=
60
2
16.6
10
3
125
400
= 0.04(Hz)