Burnham V11H Boiler Specification Sheet

Page of 4
V11H SERIES PRESSURE FIRED 
 
 
 
 
 
       BOILER-BURNER UNIT 
 
 
 
 
       SUGGESTED SPECIFICATIONS
 
 
 
Note:    To use as a project specification: 
 
             A.  Insert, in the blank spaces provided, the applicable model number, capacity,  
 
 
       fuel, and electrical data. 
 
 
 B.  Delete the item in parentheses or marked “*” which are not applicable to the  
 
 
       project requirements. 
 
 
 C.  Insert, where applicable, optional non-standard features desired.
 
1.  GENERAL SPECIFICATION 
Contractor shall furnish and install, where indicated on the drawings,  ______ (quantity) Model  
V-11H______,  ______ (steam or water), ______ (#2 Oil, Nat. or LP Gas, #2 Oil and Nat. or LP Gas) 
pressure fired boiler-burner unit(s), having an AHRI approved gross output of  ______ MBH per boiler 
and a net rating of _______ MBH with an burner capacity of _______ MBH (Gas) ______ GPH (#2 Oil).  
Boiler(s) shall be constructed of cast iron sections manufactured in accordance with ASME requirements 
for low pressure boilers and each section shall be permanently marked with the ASME symbol and the 
maximum allowable working pressures.  The boiler-burner unit shall not require a refractory combustion 
chamber and the sections shall be of wet base construction.  Further, the boiler-burner unit shall be 
designed so that only a vent shall be required that extends only 3 feet above the highest point of the roof. 
 
2.  BOILER EQUIPMENT SPECIFICATION 
    *
2.1  The boiler shall be furnished as a knocked down unit for field erection according to the              
manufacturer’s instructions. 
      *(NOTE TO SPECIFIER:  The V11H boiler-burner unit is shipped as standard with sections         
unassembled.  However, if job conditions permit, the following options are available.   
    *2.2  The boiler shall be furnished as a factory assembled and water tested section assembly with the             
jacket, burner, and controls shipped separately. 
*2.3  The boiler shall be furnished as a factory packaged boiler with jacket, burner, and controls  
         mounted and wired.  Boiler shall be mounted on a steel shipping skid and entire package shall  
         be shrink wrapped. 
    *2.4  Factory packaged boiler shall be factory firetested. 
      2.5  Boiler shall be equipped with a flange mounted flame retention forced draft burner that has been             
designed and tested for a minimum of 81.5% (Gas fired, water), 80.5% (Gas fired, steam) and/or 
84.4% (Oil fired, water), 83.5% (Oil fired, steam) thermal efficiency based on AHRI testing 
procedure.  
      2.6  The boiler-burner mounting plate shall be lined with lightweight refractory insulation and shall             
have built-in observation port with closure cover.   
      2.7  Boiler sections shall have pin-like projections on each center section, evenly spaced on the              
vertical flue with removable stainless steel flue baffles inserted between each row surfaces to extract 
the greatest possible heating value from the hot flue gases. 
      2.8  Boiler sections shall be surface ground to ensure smooth positive mating surfaces. 
      2.9  Boiler sections shall be assembled with precision machined cast iron push nipples, pressed into a 
mating machined nipple port in the section eliminating the need for any gasket material which would 
be subject to deterioration due to corrosion or oil based chemicals.  The sections are to be assembled 
with short draw rods.