Burnham Series 3 Power Flame Low NOx Data Sheet

Page of 2
Power Flame 30 PPM 
[1]
 Low Nox Burner Information
Firing
Burner Model
Sequence
Gas and Gas/#2 Oil
Blower
Oil 
Pump
A/C
Gas and 
Gas/#2 Oil
Minimum Gas 
Pressure
Maximum Gas 
Pressure
Size 
[3]
LN3-40
   LNIC2-G(O)-20A
1
1/3
N/A
Full Mod
RM7897C/UV
9.2" w.c.
14" w.c.
1.25/1
4"
LN3-50
   LNIC2-G(O)-20B
1
1/2
1/3
N/A
Full Mod
RM7840L/UV
7.7" w.c.
14" w.c.
1.5/1.25
6"
LN3-60
 LNIC3-G(O)-20
2
1/2
N/A
Full Mod
RM7840L/UV
6.9" w.c.
14" w.c.
2/1.5
6"
LN3-70
 LNIC3-G(O)-20
2
1/2
N/A
Full Mod
RM7840L/UV
8.5" w.c.
14" w.c.
2/1.5
6"
LN3-80
 LNIC3-G(O)-20
2
1/2
N/A
Full Mod
RM7840L/UV
10.6" w.c.
14" w.c.
2/1.5
6"
LN3-90
   LNIC3-G(O)-25B
3
3/4
N/A
Full Mod
RM7840L/UV
9.2" w.c.
14" w.c.
2
6"
LN3-100
 LNIC4-G(O)-30
3
1/2
N/A
Full Mod
RM7840L/UV
5" w.c.
14" w.c.
2-1/2"
8"
LN3-125
 LNIC4-G(O)-30
5
1/2
N/A
Full Mod
RM7840L/UV
6" w.c.
14" w.c.
3"
8"
LN3-150
 LNIC5-G(O)-30
7
1/2
1/2
N/A
Full Mod
RM7840L/UV
8" w.c.
28" w.c.
3"
8"
LN3-175
 LNIC5-G(O)-30
7
1/2
1/2
N/A
Full Mod
RM7840L/UV
11" w.c.
28" w.c.
3"
8"
LN3-200
 LNIC6-G(O)-30
10
1/2
N/A
Full Mod
RM7840L/UV
12" w.c.
28" w.c.
3"
10"
LN3-250
 LNIC6-G(O)-30
10
1/2
N/A
Full Mod
RM7840L/UV
16" w.c.
28" w.c.
3"
10"
LN3-300
LNICM9A-G(O)-30
5
1/2
5
Full Mod
RM7840L/UV
44" w.c.
10 psig
3"
10"
LN3-350
LNICM9A-G(O)-30
5
1/2
5
Full Mod
RM7840L/UV
44" w.c.
10 psig
3"
10"
LN3-400
LNICM9B-G(O)-30
7
1/2
1/2
5
Full Mod
RM7840L/UV
63" w.c.
10 psig
3"
12"
LN3-500
LNICM10-G(O)-30
15
3/4
5
Full Mod
RM7840L/UV
94" w.c.
10 psig
3"
14"
LN3-600
LNICM10B-G(O)-30
15
3/4
1/2
Full Mod
RM7840L/UV
115" w.c.
10 psig
3"
14"
LN3-700
LNICM10C-G(O)-30
20
3/4
1/2
Full Mod
RM7840L/UV
115" w.c.
10 psig
3"
16"
LN3-800
LNICM11-G(O)-30
25
2
15
Full Mod
RM7840L/UV
77"w.c
10 psig
3"HF
16"
LN3-900
LNICM11-G(O)-30
25
2
15
Full Mod
RM7840L/UV
77"w.c
10 psig
3"HF
16"
LN3-1000
LNICM11A-G(O)-30
30
2
15
Full Mod
RM7840L/UV
77"w.c
10 psig
3"HF
16"
Gas and Gas/#2Oil Firing Sequence 
ALL MODELS: FULL MODULATION WITH PROVEN LOW FIRE START, SYNCHRONIZED FUEL/AIR CONTROL WITH MODULATING MOTOR.
NOTES:
[1]
EXPECTED EMISSIONS ARE 30 PPMVD OR LESS NOx (CORRECTED TO 3.0% O
2
) AND 400 PPMVD OR LESS CO (CORRECTED TO 3.0% O2) WHEN 
   FIRING NATURAL GAS
[2]
 ALL BLOWER AND AIR COMPRESSOR MOTORS AVAILABLE 208-230-460/60/3, INDICATE JOBSITE  ON  ORDER.  OIL PUMP MOTORS ARE 230/60/1; 
   CONSULT FACTORY FOR OTHER VOLTAGES
[3]
DUAL SIZE GAS TRAINS: LEAK TEST COCK, MAIN GAS VALVE AND AUXILIARY GAS VALVE ARE INDICATED BY THE FIRST NUMBER. GAS REGULATOR 
   AND MAIN SHUTOFF COCK ARE INDICATED BY THE SECOND NUMBER.
Boiler Size
Standard Flame 
Safeguard
FGR 
Line
Size
Horsepower 
[2]
Motor
Gas Train
SERIES LN3 
LN-1