Burnham Series 4FH-50 Power Flame Data Sheet
Power Flame Burner Information
5.0 rating
Burner Model
Motor
Firing Sequence
[1]
Standard UL Flame Safeguard
Gas Train
Horsepower
Boiler Size
Gas and
Gas/#2 Oil
#2 Oil
Gas
#2 Oil
Gas/#2 Oil
Voltage
Gas
#2 Oil
Gas/#2 Oil
Gas
#2 Oil
Gas/#2 Oil
Size
Min. Pres. Max. Pres.
4FH-63
CR1-G(O)-10
CR1-O
1/3
1/3
120/60/1
On-Off
On-Off
RM7897A/UV
R7184P/CC
RM7897C/UV
1
4.9" w.c.
14.0" w.c.
4FH-78
CR1-G(O)-10
CR1-O
1/3
1/3
120/60/1
On-Off
On-Off
RM7897A/UV
R7184P/CC
RM7897C/UV
1
5.3" w.c.
14.0" w.c.
4FH-92
CR1-G(O)-10
CR1-O
1/3
1/2
120/60/1
On-Off
On-Off
RM7897A/UV
R7184P/CC
RM7897C/UV
1
5.7" w.c.
14.0" w.c.
4FH-107
CR1-G(O)-12
CR1-O
1/3
1/2
120/60/1
On-Off
On-Off
RM7897A/UV
R7184P/CC
RM7897C/UV
1
5.1" w.c.
14.0" w.c.
4FH-127
C2-G(O)-15
C2-OA
1/2
3/4
240/60/1
[2]
L-H-O
L-H-O
RM7897A/UV
R7184P/CC
RM7897C/UV
1
1/4
4.4" w.c.
14.0" w.c.
4FH-154
C2-G(O)-15
C2-OA
1/2
3/4
240/60/1
[2]
L-H-O
L-H-O
RM7897A/UV
R7184P/CC
RM7897C/UV
1
1/4
6.1" w.c.
14.0" w.c.
4FH-180
C2-G(O)-15
C2-OA
1/2
3/4
240/60/1
[2]
L-H-O
L-H-O
RM7897A/UV
R7184P/CC
RM7897C/UV
1
1/4
7.2" w.c.
14.0" w.c.
4FH-209
C2-G(O)-20B
C2-OB
1
1
1/2
240/60/1
L-H-O
L-H-O
RM7897A/UV
R7184P/CC
RM7897C/UV
1
1/4
8.0" w.c.
14.0" w.c.
4FH-240
C2-G(O)-20B
C2-OB
1
1
1/2
240/60/1
L-H-O
L-H-O
RM7897A/UV
R7184P/CC
RM7897C/UV
2
5.1" w.c.
14.0" w.c.
4FH-277
C2-G(O)-20B
C2-OB
1
1
1/2
240/60/1
L-H-O
L-H-O
RM7897A/UV
R7184P/CC
RM7897C/UV
2
5.8" w.c.
14.0" w.c.
4FH-311
C3-G(O)-20
C3-O
1
1/2
2
3-phase
[3]
L-H-O
L-H-O
RM7897C/UV
R7184P/CC
RM7897C/UV
2
4.8" w.c.
14.0" w.c.
4FH-345
C3-G(O)-20
C3-O
1
1/2
2
3-phase
[3]
L-H-O
L-H-O
RM7897C/UV RM7897A/UV RM7897C/UV
2
5.7" w.c.
14.0" w.c.
4FH-360
C3-G(O)-20
C3-O
1
1/2
2
3-phase
[3]
L-H-O
L-H-O
RM7897C/UV RM7897A/UV RM7897C/UV
2
5.4" w.c.
14.0" w.c.
4FH-450
C3-G(O)-25B
C3-OB
3
3
3-phase
[3]
L-H-O
L-H-O
RM7897C/UV RM7897A/UV RM7897C/UV 2 / 2
1/2[4]
8.2" w.c.
14.0" w.c.
4FH-563
C4-G(O)-30
C4-OB
5
5
3-phase
[3]
L-H-O
L-H-O
RM7897C/UV RM7897A/UV RM7897C/UV
2
1/2
7.2" w.c.
14.0" w.c.
4FH-675
C5-G(O)-30
C5-O
7
1/2
7
1/2
3-phase
[3]
Full Mod
Full Mod
RM7840L/UV RM7840L/UV RM7840L/UV
2
1/2
9.6" w.c.
14.0" w.c.
4FH-827
C5-G(O)-30
C5-O
7
1/2
7
1/2
3-phase
[3]
Full Mod
Full Mod
RM7840L/UV RM7840L/UV RM7840L/UV
2
1/2
10.4" w.c.
14.0" w.c.
4FH-993
C5-G(O)-30
C5-O
7
1/2
7
1/2
3-phase
[3]
Full Mod
Full Mod
RM7840L/UV RM7840L/UV RM7840L/UV
3
12.6" w.c.
28.0" w.c.
4FH-1157
C6-G(O)-30
C6-O
10
10
3-phase
[3]
Full Mod
Full Mod
RM7840L/UV RM7840L/UV RM7840L/UV
3
16.1" w.c.
28.0" w.c.
4FH-1323
C6-G(O)-30
C6-O
10
10
3-phase
[3]
Full Mod
Full Mod
RM7840L/UV RM7840L/UV RM7840L/UV
3
19.1" w.c.
28.0" w.c.
[1] Explanation of Firing Sequences:
Gas and Gas Sequence on Combination Gas/Oil Boilers
On-Off
On-Off
On-Off, fixed fire with slow opening gas valve, fixed air.
L-H-L
Low fire start (not proven), high fire run, Lo-Hi-Off gas valve, two stage air control.
Full Mod
Full modulation with proven low fire start.
Oil and Oil Sequence on Combination Gas/Oil Boilers
On-Off LFS
On-Off LFS
Fixed air low fire start.
L-H-O
Low fire start (not proven), high fire run, oil cylinder air control .
Full Mod
Full modulation with proven low fire start.
[2] Voltage on gas burner model is 120/60/1.
[3] On 3-phase voltage, must specify 208, 230, or 460/60/3 on order.
[4] Model 4F-450 - Dual size gas trains: Leak test cock, main gas valve and auxiliary gas valve are indicated by the first number; gas regulator and main shutoff cock
are indicated by the second number.
[3] On 3-phase voltage, must specify 208, 230, or 460/60/3 on order.
[4] Model 4F-450 - Dual size gas trains: Leak test cock, main gas valve and auxiliary gas valve are indicated by the first number; gas regulator and main shutoff cock
are indicated by the second number.
SERIES 4FH- 50
2/12