GV2 Series Control Panels | Owner's Manual Supplement  
 
 
Bosch Security Systems, Inc. | 2/07 | F01U063791-01 
23 
 
3.3 
User-Caused False Alarms, Arming the System 
3.3.1  Exit Time Defaults 
The SIA standard calls for Exit Time to range from 45 sec to at 
least two min (not to exceed 255 sec).  
The default is 60 sec. 
3.3.2 Exit 
Tone 
The SIA standard requires that the control panel provide an Exit 
Tone to alert anyone remaining in the premises that Exit Delay is 
in process. The tone pulsing rate increases during the last 10 sec 
of Exit Time. 
The Exit Tone can be disabled only for individual keypads, not for 
the entire system. 
During the last 10 sec of Exit Delay, the control panel’s Alarm Bell 
output pulses on and off for the last 10 sec of Exit Delay. 
3.3.3  Exit Time Restart 
The SIA standard requires that the control have an option that 
restarts Exit Delay if a user follows these steps: 
1.  Starts Exit Delay (arms the system) 
2.  Exits and closes an Exit Delay zone. 
3.  Returns through an Exit Delay zone. 
4.  The control panel restarts Exit Delay (one-time restart only). 
 
 
I have this feature. 
 
 
I do not have this feature. 
3.3.4 Exit 
Error 
When a user leaves an Exit Delay zone faulted at the end of Exit 
Time, the control panel creates an “Exit Error” event as specified 
by the SIA standard: 
1.  An Exit Delay point remains faulted at the end of Exit Delay. 
2.  Entry Delay starts. Keypads show 
DISARM NOW
 and the Entry 
Tone sounds.