Mitsubishi Electronics Mitsubishi Digital Electronics Insect Control Equipment FX2N-5A User Manual
FX2N-5A Special function block
Wiring 5
5-3
5.3
Output Wiring
Please refer to 5.2 for the wiring for "24+", "24-" terminals.
Figure 5.3: Output Wiring
*1 Use a twisted pair shielded cable for the
analog output. This cable should be wired
away from power lines or any other lines
which could induce noise.
away from power lines or any other lines
which could induce noise.
*2 Apply 1-point grounding at the load side of
the output cable (grounding: 100
Ω or less).
*3 If electrical noise or a voltage ripple exists at
the output, connect a smoothing capacitor of
0.1 to 0.47
0.1 to 0.47
µF, 25V.
- Shorting the voltage output terminal or
connecting the current output load to the
voltage output terminal may damage the
FX
voltage output terminal may damage the
FX
2N
-5A.
- For the terminal arrangement, refer to Section
2.
Figure 5.4: Crimp Terminals
Voltage output
V+
VI-
I+
OUT
*1
Shielded cable
Shielded cable
Current output
V+
VI-
I+
OUT
Inverter,
etc.
Recorder,
etc.
*2
*1
Shielded cable
Shielded cable
*2
FX
2N
-5A
FX
2N
-5A
*3
N.C.
6.2 mm (0.24" )
or less
For M3 (0.12")
6.2 mm (0.24")
or less
For M3 (0.12")