FX2N-5A Special function block
Buffer Memory (BFM) 7
7-40
7.2.26
BFM 55 Analog output Gain data (READ/WRITE)
Output Gain data: Analog output voltage or current if digital input in BFM 14 is 16000 (or 1000
as stated in table below) default gain value for voltage mode (-10V/+10V) is 5V (=K5000), for
current mode (4 - 20mA) is 12mA(=K12000) and for current mode (0 - 20mA) is 10mA
(=K10000).
The value of BFM 55 is stored non-volatile in the internal EEPROM. There is a safety function
to protect the internal EEPROM from being destroyed by accidentally writing the same value
continuously to BFM 55.
as stated in table below) default gain value for voltage mode (-10V/+10V) is 5V (=K5000), for
current mode (4 - 20mA) is 12mA(=K12000) and for current mode (0 - 20mA) is 10mA
(=K10000).
The value of BFM 55 is stored non-volatile in the internal EEPROM. There is a safety function
to protect the internal EEPROM from being destroyed by accidentally writing the same value
continuously to BFM 55.
Note: This table is not applicable for modes 9 to A (see Scaling function settings).
* In absolute voltage output mode, the theoretical value is 16000, however in reality it is not
possible to exceed 10V output voltage (BFM14=10000).
Table 7.10: Initial offset/gain value(Unit: mV for voltage output,
µA for current output)
BFM 14 value
for gain output
for gain output
16000
1000
16000
500
16000
500
(16000*)
16000
16000
Output mode
(BFM 1)
(BFM 1)
0
(-10V to
+10V)
1
(-10V to
+10V)
2
(4 to
20mA)
3
(4 to
20mA
4
(0 to
20mA)
5
(0 to
20mA)
6
absolute
voltage
mode
7
absolute
current
mode
8
absolute
current
mode
Initial offset
value
value
0
0
4000
4000
0
0
0 fixed
0 fixed
0 fixed
Initial gain
value
value
5000
unit:mV
5000
unit:mV
12000
unit:
µ
A
12000
unit:
µ
A
10000
unit:
µ
A
10000
unit:
µ
A
16000
fixed
unit:mV
16000
fixed
unit:
µ
A
16000
fixed
unit:
µ
A