OPERATION (cont.)
Self-Diagnostic Codes
Self-diagnostic codes are displayed on the control board under the following 
conditions.
Contact your MovinCool reseller or a qualified technician if problem persists.
LCD Display Codes
Condition
When the drain tank switch shuts off the unit, LCD 
displays “TANK FL” and “TANK FULL” LED flashes.
Once emptying the drain tank procedure is completed 
and ON/OFF has been pressed, unit returns to normal 
operation.
When the drain pump malfunctions, the compressor 
shuts off, and the LCD displays “AS”. Once drain 
pump is fixed and unit has been RESET, the unit 
returns to normal operation.
To RESET: Press FAN HI/LO and COOL ON/OFF 
buttons simultaneously for 5 seconds.
< Classic Plus 26 ONLY > When high pressure switch 
is activated, display shows “HP” if high pressure 
switch is activated 3 times in 24 hr, unit displays 
Unit returns to normal operation after problem is fixed 
and controller is RESET.
To RESET: Press FAN HI/LO and COOL ON/OFF 
buttons simultaneously for 5 seconds.
When room thermistor becomes open or shorted, 
display shows “OPEN RT” or “SHRT RT” and cool 
mode operation is off. Display and cool mode 
operation are returned to normal operation after room 
thermistor is fixed.
When freeze thermistor becomes open or shorted, 
display shows “OPEN FT” or “SHRT FT” and cool 
mode operation is off. Display and cool mode 
operation are returned to normal operation after 
freeze thermistor is fixed.
When the unit detects a signal from the fire alarm 
system, the display shows "ALRM" and a buzzer turns 
on. Check the fire alarm system and confirm that there 
is no signal input to the unit. The unit returns to the 
normal operation after the problem is fixed and the 
controller is RESET.
To RESET: Press FAN HI/LO and COOL ON/OFF 
buttons simultaneously for 5 seconds.