InRow RP Technical Data Manual
Air-cooled Data - General
Note: Reduce airflow and cooling capacity specifications by 7% for cooling units run at low input voltage (380 V).
MODEL
ACRP 100 Series
AIR SYSTEM - FAN (Standard Filter Installed)
Air Volume - l/s (SCFM)
2265 (4800)
Fan Motor - W (HP)
1100 (1.5)
Number of Fans
2
COOLING COIL - COPPER TUBE/ALUMINUM FIN
Face Area - m
2
 (ft
2
)
.56 (6.0)
Rows Deep
4
HUMIDIFICATION - SOLID STATE ELECTRODE CANISTER
Flush Cycle
automatic
Capacity - kg/hr (lbs/hr)
3 (6.6)
kW
2.25
REHEAT
Electric - Equally Loaded Two Stage, Finned Tubular, Low-Watt Density
Capacity - kW (BTU/hr)
6 (20,500)
Stages
2
FILTERS - PLEATED (STANDARD)
Quantity
3
Size - mm (in)
418 x 470 (16.45 x 18.5)
Depth - mm (in)
96 (3.78)
Efficiency (%)
30
FILTERS - PLEATED (OPTIONAL)
               Quantity
3
               Size - mm (in)
418 x 470 (16.45 x 18.5)
               Depth - mm (in)
96 (3.78)
               Efficiency (%)
85
PHYSICAL DATA
Weight - kg (lbs)
378 (833)
Height - mm (in)
1991 (78.40)
Width - mm (in)
600 (23.62)
Depth - mm (in)
1070 (42.13)
CONNECTION SIZES
Refrigerant
Discharge
7/8 in ODF brazed
    Maximum pressure drop - bar (PSI)
0.7 (10)
Liquid
7/8 in ODF brazed
Humidifier
Supply Line - mm (in)
6.35 (1/4)
Condensate Drain
Drain Line - mm (in)
12.7 (1/2)