APC Condenser 2 EC Fan ACCD75208 User Manual

Product codes
ACCD75208
Page of 50
InRow RP Technical Data Manual
38
Guide Specifications
PART 1 — GENERAL
1.01
SUMMARY
A. The environmental control system shall be designed specifically for precision temperature and 
humidity control applications. It will automatically monitor and control heating, cooling, 
humidifying, dehumidifying, and filtering functions for the conditioned space. The system shall be 
built to the highest quality engineering and manufacturing standards, and shall be floor mounted 
and configured for horizontal airflow, with draw-through air pattern, to provide uniform air 
distribution over the entire face of the coil.
1.02
DESIGN REQUIREMENTS
A. The system shall be as described in the following specification as manufactured by APC.
1 . Model: ____________________________.
2 . Total net cooling capacity: _______________ kW (MBH).
3 . Sensible net cooling capacity: ____________ kW (MBH).
4 . Return air dry bulb temperature: _______________ º C (º F) DB.
5 . Return air wet bulb temperature: _______________ º C (º F) WB.
6 . Humidity: __________________________% RH.
7 . Air Volume: _______________________ L/s (CFM).
8 . Humidifier capacity: _________________ kg/hr (lbs/hr).
9 . Electrical supply: ________ V, _________ Hz.
1.03
SUBMITTALS
A. Submittals shall be provided with the proposal and shall include: capacity data, electrical data, 
physical data, electrical connection drawing, and piping connection drawing.
1.04
QUALITY ASSURANCE
A. The system shall be factory-tested prior to shipment. Testing shall include, but not be limited to: 
complete pressure and leak testing to ensure system integrity, “Hi-Pot” test, and controls 
calibration and settings. The system shall be NRTL listed, MCA, and electrical system shall be UL 
Listed to UL 1995 and CSA 22.2 No. 236.
1.05
WARRANTY
A. System parts shall be warranted for a period of 18 months from date of shipment and 12 months 
from startup.
PART 2 — PRODUCT
2.01
STANDARD COMPONENTS
A. CABINET CONSTRUCTION
1 . Exterior panels shall be 1.2 mm (18 gauge) steel. Front and rear exterior panels shall be 
1.2 mm (18 gauge) perforated steel with 69.5% open free area, and equipped with a keyed lock 
to provide a means of securing access to the internal components of the unit. 
2 . The frame shall be constructed of 1.5 mm (16 gauge) formed steel welded for maximum 
strength. All units shall provide maintenance from the front and rear, allowing units to be 
placed within a row of racks. 
3 . All exterior panels and frame shall be powder coated for durability and attractive finish. 
Exterior frame and panel color shall have color values: L = 74.50, a = -.53, b = +8.20.
4 . Units shall include casters and leveling feet to allow ease of installation in the row and provide 
a means to level the equipment with adjacent IT racks.