APC Condenser 2 EC Fan ACCD75208 User Manual

Product codes
ACCD75208
Page of 50
1
InRow RP Technical Data Manual
Overview
The modular, row-based computer 
room cooling system offers efficient, 
predictable, and economical cooling 
for a variety of spaces.
Critical environmental requirements 
now reach far beyond the confines of 
the traditional data center or 
computer room to encompass a larger 
suite of applications, referred to as 
technology rooms. Critical 
environment applications include:
•  Computer rooms
•  Telecommunication facilities
•  Clean rooms
•  Power equipment
•  Medical equipment rooms
•  LAN/WAN environments
A worldwide network of APC 
representatives is fully qualified to 
provide engineering, sales, 
installation, and service for our 
products.
APC warrants all parts for 18 months 
from shipment and 12 months from 
startup. Extended warranties are 
available.
Capacity
The InRow RP chilled water 
configuration is available in one size 
with a capacity that is up to 60 kW 
based on the particular application of 
the unit. The InRow RP air-cooled 
configuration is available in one size 
with a capacity that is up to 37 kW.
Room Air Distribution
Row-based systems are placed in line 
with rack enclosures. At least one 
system is used per hot aisle. Air is 
drawn in through the rear of the 
system, cooled, and discharged into 
the cold aisle, thereby neutralizing 
the sensible heating effects of the 
data processing equipment.The 
InRow RP delivers high volumes of 
airflow to eliminate hot spots in 
densely populated environments.
Configuration
•  Chilled Water
•  Air-cooled
Compliance Approval
•   UL  Listed
•  VDE
•   CE
•   C-tick
•   C-UL  Listed
Chilled Water Standard 
Features
•  Insulated cabinet
•  Backward inclined impeller
•  Variable speed fans (3)
•  Shutdown input/alarm output
•  Chilled water flow meter
•  2-way/3-way floating point valve
•   Humidifier
•  Counter flow cooling coil
•  Electric reheat
•  Pleated 100 mm (4 in) filter
•  NPT to BSPT pipe adapters
•  Top or bottom piping
•  Condensate management with dual 
position float
•  Network management card
•  Baying Kit InRow RP to 
NetShelter® SX rack
•  Remote temperature sensor (3)
•  Microprocessor controller
•  Automatic transfer switch
Air-cooled Standard 
Features
•  Insulated cabinet
•  Backward inclined impeller
•  Variable speed fans (2)
•  Shutdown input/alarm output
•   Humidifier
•  Cross circuited cooling coil
•   Electric  reheat
•  Pleated 100 mm (4 in) filter
•   Pipe  adapters
•  Top or bottom piping
•  Condensate management with dual 
position float
•  Network management card
•  Baying kit InRow RP to 
NetShelter
®
 SX rack
•  Remote temperature sensor (3)
•  Microprocessor controller
•  Variable speed reciprocating 
compressor using VFD control
•  Liquid line solenoid valve
•  Pressure equalization solenoid
Accessories
•  Cable leak detector
•  Baying kit InRow RP to NetShelter 
VX rack
•  NetShelter SX 42U to 48U height 
adapters
•  NetShelter VX 42U height adapters
•  Bridge trough power cable shield
•  Data cable bridge partition
•  Flex hose piping kits