Compressor Stop Mode (B)
Operating Mode Selection (C, D)
Economizer Control Mode (E)
CONTROL_MODE_SW
Setting
Input A
Input B
Operating Mode Description
B
OFF
OFF
Indoor unit operating (Compressor in stop mode), locked
ON
OFF
Indoor unit prior operating condition maintained (Compressor not in stop mode), 
unlocked
OFF
ON
Indoor unit stopped, locked
ON
ON
Indoor unit stopped, locked
CONTROL_MODE_SW
Setting
Input A
Input B
Operating Mode Description
C
OFF
OFF
Indoor unit stopped, unlocked
ON
OFF
Indoor unit operating in cool mode / fan high, unlocked
OFF
ON
Indoor unit operating in heat mode / fan high, unlocked
ON
ON
Indoor unit operating in fan high, unlocked
D
OFF
OFF
Indoor unit stopped, locked
ON
OFF
Indoor unit operating in cool mode / fan high, locked
OFF
ON
Indoor unit operating in heat mode / fan high, locked
ON
ON
Indoor unit operating in fan high, locked
CONTROL_MODE_SW
Setting
Input A
Input B
Operating Mode Description
E
OFF
OFF
Indoor unit prior operating condition maintained, unlocked
ON
OFF
Indoor unit operating with thermal off in cooling mode, unlocked
OFF
ON
Indoor unit prior operating condition maintained, unlocked
ON
ON
Indoor unit operating with thermal off in cooling mode, unlocked