LG PQDSBC1 Owner's Manual

Page of 14
5
Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.  
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
UNIT DESCRIPTION
Dry Contact with Economizer Interface
This manual describes how to install and configure the Dry Contact with Economizer Interface, Model PQDSBC1. The dry contact is used with  
LG Electronics’ Variable Refrigerant Flow (VRF) Systems. The Economizer is an indoor unit (IDU) that allows or prevents outside air entering conditioned 
spaces through the air ducts of the VRF system. To economically help satisfy conditioned zones that call for cooling, the Economizer routes cool outside 
air through the ducted system to these zones. For zones that call for heating, the dry contact control prevents the Economizer from routing outside air to 
those spaces. The dry contact controls Economizer operation according to its internal control settings and external control signals. 
Note:
 
Your indoor unit may require a firmware update to be compatible with the Dry Contact with Economizer Interface. 
Contact your local LG representative for additional information.
Other Dry Contact Functions
In addition to controlling an Economizer, the dry contact can be configured to interface with other types of indoor units such as high and low 
static ducted units and vertical air handlers. Configure the dry contact as necessary for your system.
Component Parts
Figure 1 shows dry contact components. The dry contact is composed of a plastic 
case, an internal printed circuit board (PCB), a communications cable (not shown), 
and controls on the internal PCB. These components are connected and config-
ured during the installation procedure.
Dry Contact Assembly
Top
Bottom
Item
PCB Component
Description
1
CN_INDOOR
Connector for the included dry contact to indoor unit cable.
2
CN_PI485
PI485 connector. Used only with PI485 PCB (additional component, not included)
3
CHANGE_OVER_SW
Must be set to match voltage applied to input terminals A, B, and common.
4
CN_CONTROL
Terminals for two contact closure input signals: A, B, and common.
5
CONTROL_MODE_SW Rotary switch. Selects dry contact unit function.
6
SETTING_SW
DIP switch. Set as necessary for your system.
7
TEMP_SETTING
Rotary switch. Selects temperature setpoint for the connected indoor unit.
8*
CN_OUT (O1, O2)
Two terminal connections. In mode E (economizer), outputs Cooling Thermal Mode On signal when cooling is 
demanded. In all other modes, if indoor unit is operating, contact closes and outputs an indoor unit ON status signal.
9*
CN_OUT (E3, E4)
Two terminal connections. Not used in operating mode E (economizer). In all other operating modes, if the indoor 
unit has an operational error, contact closes and outputs a signal.
10
DISPLAY_LED
LED that displays the operational and communication status of the dry contact.
11
RESET_SW
Pushbutton reset switch.
Table 1:  PCB Connectors and Controls
Figure 1:  Dry Contact Components
* Outputs function differently depending on configured mode.
Printed Circuit Board
NOT
USED
e
CN_OUT
CHANG
E
OVER_S
W
VOLT
NON
VOLT
TEMP
SETTING
1
2
5
8
9
7
3
6
11
10
4
COM A B
O1 O2 E3 E4