Dacor DTO230S208V Installation Instruction

Page of 36
10
Installation Instructions
Electrical Connection - (continued)
Connecting to a Three Wire Electrical 
System - Where Local Codes Permit
 WARNING
Do not connect the green appliance conduit wire to the 
neutral (white) junction box wire unless local building 
codes permit.
1.  Separate the wires coming out of the appliance conduit.
2.  Connect the green and white wires from the appliance 
conduit to the white (neutral) supply wire in the junction 
box.
3.  Connect the black wire from the appliance conduit to 
the black (L1) supply wire in the junction box.
4.  Connect the red wire from the appliance conduit to the 
red (L2) supply wire in the junction box.
Connecting to a Three Wire Electrical 
System with External Ground - Where Local 
Codes Permit
 WARNING
•  Do not ground the appliance to a gas supply pipe or 
hot water pipe.
•  If connecting the ground wire to a grounded cold water 
pipe, connect using a separate copper grounding 
wire (No. 10 minimum) and a clamp with an external 
grounding screw. The grounded cold water pipe must 
have metal continuity to electrical ground and must not 
be interrupted by insulating materials. Any insulating 
materials must be jumped, with a minimum, 4 AWG 
wire to establish continuity to ground. See facing page.
 NOTE
If the junction box has been properly grounded by a 
licensed electrician, the green (ground) wire from the 
appliance conduit may be connected to the junction box 
using a loop terminal.
To connect the green appliance conduit wire to a 
grounded cold water pipe, see diagrams on facing 
page.
1.  Separate the wires coming out of the appliance conduit.
2.  Connect the white wire from the appliance conduit to 
the white (neutral) supply wire in the junction box.
3.  Connect the black wire from the appliance conduit to 
the black (L1) supply wire in the junction box.
4.  Connect the red wire from the appliance conduit to the 
red (L2) supply wire in the junction box.
5.  Connect the green wire from the appliance conduit to a 
grounded cold water pipe as shown. Jumper any insu-
lating materials as shown above with a length of No. 4 
copper wire. Securely clamp the wire to bare metal at 
both ends.
Incoming power
Wire nut,
3 places
Junction box
Conduit to  
oven
Three Wire Connection
RED
RED
WHITE
WHITE
GREEN
BLACK
BLACK