LG PQNFB17C1 Specification Sheet

Page of 3
Date:
Job Name/Location:
PO No.:
Architect:
Engr:
GC:
Rep:
For:
File
Approval
Mech:
Resubmit
Other
(Company)
(Project Manager)
Tag #:
PQNFB17C1
ACP BACnet® Gateway
Standard Features:
Electrical:
Power Consumption
22 VA
Unit Data:
 
1.When combined with AC Smart Premium or PDI, 128 max devices per V‐Net.
 
2.PI‐485 adapter required. Contact Engineering for a list of compa ble systems.
Must follow installation instructions in the applicable LG installation manual.
Notes:
Optional Accessories (sold separately)
Digital Output Kit ‐ PQNFP00T0
Surrounding Conditions:
Operating Temperature
‐4 ‐ 140°F
Storage Temperature
‐4 ‐ 176°F
Dimensions
10‐11/16" W x 6‐3/16" H x 2‐5/8" D
Maximum Number of Outdoor Units
64 (16 per V‐Net)
 
•Integrates Mul  V and select Mini and Mul  Split systems² with third party building 
management systems.
 
•BTL cer fied (ASHRAE 135‐2004) BACnet® Applica on Specific Controller (B‐ASC)
 
•Supports registra on as a foreign device
 
•20 x 4 character LCD
 
•Indoor unit control/monitoring by groups/indoor units
 
•Web access with user access control
 
•Opera on and error history log
 
•Forced off digital input
 
•Nine digital inputs and four digital outputs for device interlocking
Basic Unit Functions
Advanced Unit Functions:
Power Supply
24 VAC 60 Hz
Connectivity:
LG Communications
4 Channel/RS‐485 V‐Net
Communications Cabling Specifications (V‐Net):
Type 2‐conductor, stranded, shielded copper cable/PVC or vinyl jacket
Size
AWG 18 x 2
Maximum Length
3,280 ft (end to end)
Description:
Humidity 
0‐95% (non‐condensing)
For continual product development, LG reserves the right to change specifications without notice.
Page 1 of 3
CTRL‐SB‐CH‐002‐US 014C18
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com
AWG ‐ American Wire Gauge
Power Distribution Indicator (PDI) ‐ PQNUD1S41
Maximum Number of Devices
256 (64 per V‐Net¹)
1
Cover
2
RS‐232 Console Port
3
24 VAC Power Terminals
4
Buttons and LCD Display
5
Digital I/O and RS‐485 
Expansion Port
6
RS‐485 V‐Net Ports
7
Mini USB Port
8
USB Port
9
SD Card Slot
10 Ethernet Port
11 Power Switch
 40 VA transformer recommended.
Ethernet
10/100 BASE‐T
 
•Opera on – On/Off
 
•Mode – Auto/Cool/Dry/Heat/Fan Only
 
•Setpoint
 
•Fan Speed – Auto/Low/Med/High/Power
 
•Louver Swing
 
•Two Setpoint Auto‐Changeover
 
•Two Setpoint Setback
 
•200 Programmable Schedule Events with control of setpoint, On/Off, Mode, Fan 
Speed, Controller Lock, and Louver Swing
 
•Temperature Setpoint Range Limit
 
•Remote Controller Lock (All, Setpoint, Mode, Fan Speed)
 
•Run Time Limit (Unoccupied Override)
 
•So ware Device Interlocking
 
•Manual Control and Scheduling of Digital Output Kit
 
•Peak Control
 
•Visual Floorplan Naviga on
 
•Power Distribu on Indicator (PDI) (op onal)
PI‐485 V‐Net Interface Adapter for DFS ‐ PMNFP14A0
BMS Communications
BACnet/IP (Annex‐J)