PMBD3630
3ͲPortBranchDistributionUnit(BDUnit)
Page1of2
DFSͲSBͲGCͲ002ͲUS012K17
Forcontinualproductdevelopment,LGreservestherighttochangespecificationswithoutnotice.
LGElectronicsU.S.A.,Inc.,EnglewoodCliffs,NJ.Allrightsreserved.““LGLife’’sGood””isaregisteredtrademarkofLGCorp./www.lghvac.com
Performance:
Electrical:
PowerSupply(V¹/Hz/Ø)
208Ͳ230/60/1
PowerInput(W)
10
RatedAmps(A)
0.1
Piping:
LiquidLine(in,OD)
3/8
VaporLine(in,OD)
3/4
PipingConnectiontoOutdoorUnit:
PipingConnectiontoIndoorUnit:
LiquidLine(in,OD)
1/4(Qty3)
VaporLine(in,OD)
3/8(Qty3)
UnitData:
NetWeight(lbs)
15
ShippingWeight(lbs)
17
CommunicationCabletoIDUs²(NoxAWG)
4x18
CommunicationCabletoODUs²(NoxAWG)
4x16
IDUͲIndoorUnitODUͲOutdoorUnit
StandardFeatures:
 
••Distributesrefrigeranttoindoorunits
 
••Internalcomponentsareinsulated
 
••FlarejointsprovidedforeasyinstallaƟon
 
••Compactdesign
Notes:
 
1.AcceptableoperaƟngvoltage:187VͲ253V.
 
2.AllcommunicaƟoncabletobeminimum18AWG,2Ͳconductor,stranded,shieldedand
mustcomplywithapplicablelocalandnationalcode.
 
3.Pipinglengths:
 
••MaximumheightdiīerencebetweenBDunitandindoorunitsͲ32.8Ō
 
••MaximumheightdiīerencebetweenBDunitandBDunitͲ49.2Ō.
 
••MaximumpipinglengthbetweenBDunitandindoorunitsͲ49.2Ō
 
4.TheBDunitshouldbeinstalledinsideofabuilding.
 
5.MustfollowinstallaƟoninstrucƟonsintheapplicableLGinstallaƟonmanual.
 
6.PowerwiringcablesizemustcomplywiththeapplicablelocalandnaƟonalcode.
MaxPortCapacityBtu/h(eachport)
24,000
MaxUnitCapacityBtu/h(sumofports)
72,000