Installation Requirements
       IMPORTANT
This dryer is internally grounded to neutral unless it 
was manufactured for sale in Canada.
Only a 4-conductor cord shall be used when the 
appliance is installed in a location where grounding 
through the neutral conductor is prohibited. 
Grounding through the neutral link is prohibited for: 
(1) new branch circuit installations, (2) mobile homes, 
(3) recreational vehicles, and (4) areas where local 
codes do not permit grounding through the neutral.
       NOTE
Dryers manufactured for sale in Canada have 
factory-installed, 4-wire power supply cord 
(NEMA 14-30R).
Electrical system requirements
ELECTRICAL REQUIREMENTS FOR ELECTRIC 
DRYER:
CIRCUIT - Individual 30 amp. branch circuit 
fused with 30 amp. time delay fuses or circuit 
breakers. Use separately fused circuits for 
washer and dryer. DO NOT operate a washer 
and a dryer on the same circuit.
POWER SUPPLY - 3-wire or 4-wire, 240 volt, 
single phase, 60 Hz, Alternating Current.
3-WIRE POWER SUPPLY CORD KIT (not supplied)
OUTLET RECEPTACLE - NEMA 10-30R or NEMA 
14-30R receptacle to be located so the power 
supply cord is accessible when the dryer is in the 
installed position.
GROUNDING CONNECTION - See “Grounding 
requirements” in Electrical Installation section.
The dryer MUST employ a 3-conductor power 
supply cord NEMA 10-30 type SRDT rated at 
240 volt AC minimum, 30 amp, with 3 open 
end spade lug connectors with upturned ends 
or closed loop connectors and marked for use 
with clothes dryers. For 3-wire cord connection 
instructions see ELECTRICAL CONNECTIONS 
FOR A 3-WIRE SYSTEM.
4-WIRE POWER SUPPLY CORD KIT (not supplied)
The dryer MUST employ a 4-conductor power 
supply cord NEMA 14-30 type SRDT or ST (as 
required) rated at 240 volt AC minimum, 30 amp, 
with 4 open end spade lug connectors with 
upturned ends or closed loop connectors and 
marked for use with clothes dryers. For 4-wire 
cord connection instructions see ELECTRICAL 
CONNECTIONS FOR A 4-WIRE SYSTEM.
ELECTRICAL REQUIREMENTS FOR GAS DRYER:
CIRCUIT -  Individual, properly polarized and 
grounded 15 amp. branch circuit fused with 15 
amp. time delay fuse or circuit breaker.
POWER SUPPLY - 2-wire, with ground, 120 volt, 
single phase, 60 Hz, Alternating Current. 
POWER SUPPLY CORD - The dryer is equipped 
with a 120 volt 3-wire power cord. 
GROUNDING CONNECTION - See “Grounding 
requirements” in Electrical Installation section. 
Grounding type
Grounding type
wa
wall receptacl
ll receptacle
Po
Power cord with
wer cord with
3-prong 
3-prong  gr
grounded plug
ounded plug
Do not,
Do not, under
under
an
any cir
y circumstances,
cumstances,
cut,
cut, remo
remove
ve,
or b
or bypass th
ypass the
gr
grounding pr
ounding prong.
ong.
3-wire receptacle
(NEMA type 10-30R)
4-wire receptacle
(NEMA type 14-30R)
       NOTE
Because of potentially inconsistent voltage 
capabilities, the use of this dryer with power 
created by gas powered generators, solar 
powered generators, wind powered generators 
or any other generator other than the local utility 
company is not recommended.