Whirlpool WOD97ES0ES Specification Guide

Page of 2
PRODUCT MODEL NUMBERS
WOD97ES0E WOS97ES0E
ELECTRICAL CONNECTION
To properly install your oven, you must determine the type 
electrical connection you will be using and follow the instructions 
provided for it here.
 
Oven must be connected to the proper electrical voltage 
and frequency as specified on the model/serial/rating plate. 
The model/serial/rating plate is located under the control panel 
on single ovens and under the control panel on the upper 
oven cavity on double ovens. See the following illustrations.
 
Models rated from 7.3 to 9.6 kW at 240 volts (5.4 to 7.4 kW 
at 208 volts) require a separate 40-amp circuit. Models 
rated at 4.8 kW and below at 240 volts (3.6 kW and below 
at 208 volts) require a separate 20-amp circuit.
 
A circuit breaker is recommended.
 
If the house has aluminum wiring, follow the procedure below:
1.  Connect a section of solid copper wire to the ends 
of the flexible conduit leads.
2.  Connect the aluminum wiring to the added section 
of copper wire using special connectors and/or tools 
designed and UL-listed for joining copper to aluminum.
Follow the electrical connector manufacturer’s recommended 
procedure. Aluminum/copper connection  must conform 
with local codes and industry-accepted wiring practices.
For power requirements for models, refer to the following table.
Built-in Oven
Because Whirlpool Corporation policy includes a continuous commitment to improve 
our products, we reserve the right to change materials and specifications without notice.
Dimensions are for planning purposes only. For complete details, see Installation 
Instructions packed with product. Specifications subject to change without notice.
Ref. W10777368B 
8/15
A
A
Voltage
Single Convect
Double Convect
240 VAC
4.1 kW
8.3kW
208 VAC
3.1 kW
6.3 kW
240 VAC
17.2 A
34.2 A
208 VAC
15.0 A
29.9 A
PRODUCT DIMENSIONS — SINGLE OVENS
Single Oven
A.  Model/serial/rating plate
Double Oven
A.  Model/serial/rating plate
A. 28³⁄v" (72.8 cm) max. overall height
B. 28
M⁄zn" (72.2 cm) max. recessed width
C. 26
³⁄v" (67.9 cm) recessed height
D. 23
Z⁄v" (59.1 cm) max. recessed depth
E.  30" (76.2 cm) overall width
F.  12" (30.5 cm) from back of control panel 
to start of strain relief
G. 48" (121.9 cm) flexible conduit length
Page 1 of 2