OceanAire 2OACH3634 Manual
Three Phase Monitor
Three-Phase units can be equipped with monitors for compressor protection.
The Oceanaire Three-phase Monitor safeguards the unit against incorrect
compressor rotation, low-voltage and/or loss of power in any one of the power
The Oceanaire Three-phase Monitor safeguards the unit against incorrect
compressor rotation, low-voltage and/or loss of power in any one of the power
legs. The monitor is installed in the control box and is equipped with an LED
for diagnosis of an improper electrical condition (see diagrams below). When
power is connected, the compressor WILL NOT power up, until the monitor
for diagnosis of an improper electrical condition (see diagrams below). When
power is connected, the compressor WILL NOT power up, until the monitor
start delay has been timed out. If the compressor does not power up, an
electrical condition may need to be addressed. Remove the control box cover
and check the observe the LED on the phase monitor. The LED signals the
following:
electrical condition may need to be addressed. Remove the control box cover
and check the observe the LED on the phase monitor. The LED signals the
following:
GREEN - Proper Operation
RED/GREEN-BLINKING signals reverse phase rotation. Switch any two of the
power leads for the unit, NOT THE MONITOR LEADS, and re-start.
power leads for the unit, NOT THE MONITOR LEADS, and re-start.
RED-BLINKING signals improper voltage and/or phase loss. Correct the
power problem, then re-start the unit.
power problem, then re-start the unit.
In the event of a power interruption, the unit will re-set to a start-up condition.
The Phase Monitor will not allow the compressor to start until power is
corrected.
corrected.
GREEN-BLINKING - Start delay, 120 sec.
NOTICE
UNIT IS EQUIPPED WITH 3-PHASE POWER
MONITOR (WITH LED)
LED INDICATION
GREEN (BLINKING) = START DELAY
GREEN = PROPER OPERATION
RED/GREEN/BLINKING = PHASE REVERSAL
RED (BLINKING) = IMPROPER LEG VOLTAGE
OR PHASE LOSS
START DELAY = 120 SECONDS
LED
32