Service manual 
23 
 
 
7.4 
Air purging of the piping and indoor unit 
Required tools: 
Hexagonal wrench; adjustable wrench; torque wrenches, wrench to hold the joints and gas leak 
detector. 
Note: 
The air in the indoor unit and in the piping must be purged. If air remains in the refrigeration piping, 
it will affect the compressor, reduce the cooling capacity, and could lead to a malfunction of unit. 
Be sure, using a torque wrench to tighten the service port cap (after using the service port), so that 
it prevents the gas leakage from the refrigeration cycle. 
 
Procedure 
Recheck the piping connections. 
Open the valve stem of the 2-way valve 
counterclockwise approximately 90’, wait 10 
seconds, and then set it to closed position. 
Be sure to use a hexagonal wrench to operate 
the valve stem 
Check for gas leakage. 
Check the flare connection for gas leakage 
Purge the air from the system. 
Set the 2-way valve to the open position and 
remove the cap from the 3-way valve’s service 
port. 
Using the hexagonal wrench to press the 
valve core pin, discharge for three seconds 
and then wait for one minute. 
Use torque wrench to tighten the service port 
cap to a torque of 1.8 kg.m. (18n.m) 
Set the 3-way valve to the opened position. 
Mounted the valve stem nuts to the 2-way and 
3-way valves. 
Check for gas leakage. 
At this time, especially check for gas leakage 
from the 2-way and 3-way stem nuts, and from 
the service port. 
 
Caution: 
If gas leakage is discovered in step (3) above, 
take the following measures. 
If the leaks stop when the piping connections 
are tightened further, continue working from 
step (4). 
If the gas leaks do not stop when the 
connections are retightened, repair the 
location of the leak, discharge all of the gas 
through the service port, and then recharge 
with the specified amount of gas from a gas 
cylinder.