7.7 
Balance refrigerant of the 2-way, 3-way valves 
 
Procedure: 
Confirm that both the 2-way and 3-way valves are set to the open position. 
Connect the charge set to the 3-way valve’s service port. 
Leave the valve on the charge set closed. 
Connect the charge hose with the push pin to the service port. 
Open the valves (Low side) on the charge set and discharge the refrigerant until the gauge indicates 0.05 
to 0.1 Mpa. 
If there is no air in the refrigeration cycle [the pressure when the air conditioner is not running is higher 
than 0.1Mpa, discharge the refrigerant until the gauge indicates 0.05 to 0.1 Mpa. If this is the case, it will 
not be necessary to apply a evacuation. 
Discharge the refrigeration gradually; if it is discharged too suddenly, the refrigeration oil sill be 
discharged.