8.  Electronic function 
8.1 
  Proper symbols and their meaning 
TA: Indoor ambient temperature 
TE: Indoor evaporator temperature 
TS: Setting temperature through the remote controller 
I
3sec
: Self-protection amp of compressor, continue three seconds until turns off the compressor. 
I
5MIN
: Self-protection amp of compressor, continue five minutes until turns off the compressor. 
I
FAN
: Self-protection amp of outdoor fan/indoor fans when they change from higher wind to lower wind. 
I
RESTORE
: Amp self-protection return value 
TH
DEFROST
: High wind, defrosting temperature difference 
TM
DEFROST
: Middle wind, defrosting temperature difference 
TL
DEFROST
: Low wind, defrosting temperature difference 
TE1: Anti-cold wind, from Fan Off to Breeze temperature 
TE2: Anti-cold wind, from Breeze to Setting Fan Speed temperature 
TE3: Anti-cold wind, from Setting Fan Speed to Breeze temperature 
TE4: Anti-cold wind, from Breeze to Fan Off temperature 
TE5: Evaporator low temperature protection entering temperature 
TE6: Evaporator low temperature protection restoring temperature 
TE7: Evaporator high temperature protection, compressor off temperature 
TE8: Evaporator high temperature protection, fan off temperature 
TE9: Evaporator high temperature protection, restoring temperature 
 
8.2 
  Function 
Remote receiving 
Testing and forced running 
Position set for indoor unit wind vane 
LED displaying and alarm 
On or off Timer 
Protection for the compressor 
Current protection 
High temperature protection of indoor heat exchanger at heating mode 
Auto defrosting and heating recovery at heating mode 
Anti cold air at heating mode 
Anti frozen at cooling mode 
 
8.3 
  Protection 
8.3.1  3 minutes delay at restart for compressor. 
8.3.2  Sensor protection at open circuit and breaking disconnection 
8.3.3  Fan Speed is out of control.  When Indoor Fan Speed is too high(higher than 2100RPM)or too 
low(lower than 300RPM)
 
lasting 50 seconds, the unit stops and LED displays failure information and 
can’t returns to normal operation automatically. 
8.3.4  Cross Zero signal error warning. If there is no Cross Zero signals in 4 minutes, the unit stops and 
LED displays failure information and can’t returns to normal operation automatically. 
8.3.5  The current protection of the compressor